SE100K Inverter Specifications
Three Phase Inverter with Synergy
Technology for the 277/480V Grid for North America
SE66.6KUS / SE100KUS
© SolarEdge Technologies, Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All
other trademarks mentioned herein are trademarks of their respective owners. Date: 03/2019/V01/ENG NA. Subject to change without notice.
SE66.6KUS SE100KUS
OUTPUT
Rated AC Power Output 66600 100000 VA
Maximum AC Power Output 66600 100000 VA
AC Output Line Connections 4-wire WYE (L1-L2-L3-N) plus PE
AC Output Voltage Minimum-Nominal-Maximum
(1)
(L-N) 244 - 277 - 305 Vac
AC Output Voltage Minimum-Nominal-Maximum
(1)
(L-L) 422.5 - 480 - 529 Vac
AC Frequency Min-Nom-Max
(1)
59.3 - 60 - 60.5 Hz
Maximum Continuous Output Current (per Phase) @277V 80 120 A
GFDI Threshold 1 A
Utility Monitoring, Islanding Protection, Congurable Power Factor,
Country Congurable Thresholds
Ye s
INPUT
Maximum DC Power (Module STC) / Unit 90000 / 45000 135000 / 45000 W
Transformer-less, Ungrounded Ye s
Maximum Input Voltage DC to Gnd 500 Vdc
Maximum Input Voltage DC+ to DC- 1000 Vdc
Nominal Input Voltage DC to Gnd 425 Vdc
Nominal Input Voltage DC+ to DC- 850 Vdc
Maximum Input Current 80 120 Adc
Maximum Input Short Circuit Current 120 Adc
Reverse-Polarity Protection Ye s
Ground-Fault Isolation Detection 350kΩ Sensitivity per Unit
CEC Weighted Eciency 98.5 %
Nighttime Power Consumption < 12 W
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, Cellular GSM (optional)
Rapid Shutdown NEC2014 and NEC2017 compliant/certied, upon AC Grid Disconnect
RS485 Surge Protection Built-in
DC SAFETY SWITCH
DC Disconnect 1000V / 2 x 40A 1000V / 3 x 40A
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, UL1998, CSA 2.22
Grid Connection Standards IEEE 1547, Rule 21, Rule 14 (HI)
Emissions FCC part15 class A
INSTALLATION SPECIFICATIONS
Number of units 2 3
AC Output Conduit Size / Max AWG / Max PE AWG 1.5” / 2/0 / 6 2” / 4/0 / 4
DC Output Conduit Size / Terminal Block AWG Range /
Number of Strings
(2)
2 x 1.25” / 6-14 / 6 strings 2 x 1.25” / 6-14 / 9 strings
Dimensions (H x W x D)
Primary Unit: 37 x 12.5 x 10.5 / 940 x 315 x 260;
Secondary Unit: 21 x 12.5 x 10.5 / 540 x 315 x 260
in / mm
Weight Primary Unit: 105.8 / 48; Secondary Unit 99.2 / 45 lb / kg
Operating Temperature Range -40 to +140 / -40 to +60
(3)
F / ˚C
Cooling Fan (user replaceable)
Noise < 60 dBA
Protection Rating NEMA 3R
Mounting Bracket provided
(1)
For other regional settings please contact SolarEdge support
(2)
Single input option per unit (up to 3AWG) available
(3)
De-rating from 50 C