Installation Manual

Three Phase Inverter with synergy technology - Technical
Specifications
Three Phase Inverters for the 277/480V Grid
Three Phase Inverters for
the 208V Grid
SE66.6KUS SE100KUS SE43.2KUS Units
OUTPUT
Rated AC power output 66600 100000 43200 VA
Maximum AC power output 66600 100000 43200 VA
AC Output Line Connections 4-wire WYE (l1-L2-L3) plus PE
4-wire WYE (l1-L2-L3) plus PE or
3 wire Delta
AC output voltage minimum-nominal-maximum (L-N)
1
244-277-305 105-120-132.5 Vac
AC output voltage minimum-nominal-maximum (L-L)
1
422.5-480-529 182-208-229 Vac
AC frequency min-nom-max
1
59.3-60-60.5 59.3-60-60.5 Hz
Max. continuous output current (per Phase)@277V 80 120 A
GFDI threshold 1 A
Utility monitoring, islanding protection ,
Configurable Power Factor, country configurable
Thresholds
Yes
INPUT
Maximum DC power (Module STC) 90000 /45000 135000/45000 58200/19400 W
Transformer-less, ungrounded Yes
1
For other regional settings please contact SoalrEdge support
1
Three Phase Inverter with synergy technology - Technical Specifications
Three Phase Inverter with synergy technology Guide MAN-01-00475-1.1