To configure the RS485 bus:
Allinvertersareconfiguredbydefaultasslaves.Toconfigurethemaster:
1. VerifytheON/OFF/PswitchisOFF.
2. VerifytheACison.
3. TurnONtheConnectionUnit.
4. UseSetApptoaccesstheCommissioningmainmenuscreenasdescribedinCommunicationonpage
42.
5.
FromthemainmenutapCommunication.TheCommunicationscreenisdisplayed:
Communication
Server LAN
LAN DHCP
RS485-1 SolarEdge Slave
RS485-2
Multi -Device
(Modbus)
ZigBee
Home Automation
Master
Wi-Fi SEDG-7E129A09-33
RS232 SolarEdge GSM
Cellular N/A
GPIO RRCR
Modbus
TCPport
Disable
6.
Selectthefollowingtoconfiguretheconnection:
l ServerèLAN
l RS485-1èProtocolè SolarEdge Master
l RS485-1èSlave Detect
ThesystemstartsautomaticdetectionoftheSolarEdgeslaveinvertersconnectedtothemaster
inverter.Theinvertershouldreportthecorrectnumberofslaves.Ifitdoesnot,verifytheconnections
andterminations.
RS485-1
Protocol SolarEdge (Master)