Installation Manual
Main Inverter Status
Status
Inverter
SN 07318000C
Power
100 kW
Voltage
277 Vac
Frequency
60.9 Hz
P_OK: 138 of 141
Optimizers Connected
S_OK
Server Connected
Status
Production
Switch
OFF
CosPhi
1.00
Limit
No Limit
Country
USA2
Voltage
850 Vdc
Temp
156 F
Fan
OK
Switch Off. Production disabled ›
Commissioning
l Inverter:Theinverterserialnumber
l Power:TheACoutputpower
l Voltage (Vac):TheACoutputvoltage
l Frequency:TheACoutputfrequency
l P_OK: xxx of yyy: Thereisaconnectiontothepoweroptimizersandatleastonepoweroptimizeris
sendingmonitoringdata.XXXisthenumberofpoweroptimizersforwhichtelemetrieshavebeen
receivedinthelasttwohours.YYYisthenumberofpairedpoweroptimizersidentifiedduringthe
mostrecentpairingprocess.IfXXXandYYYarenotequal,theremaybeaprobleminoneormore
poweroptimizers.
l S_OK:TheconnectiontotheSolarEdgemonitoringplatformissuccessful(appearsonlyiftheinverter
isconnectedtothemonitoringplatform).
l Status: Theinverteroperationstatus:Off,NotPaired,NightMode,Error,Pairing,orProduction
l Switch:IndicatesthepositionoftheinverterON/OFF/Pswitch:On,Off,orPposition.
l CosPhi:Indicatestheratiobetweenactiveandreactivepower.Anegativevalueindicatesalagging
CosPhi.
Formoreinformation,refertothePowerControlApplicationNote,availableonthe
SolarEdgewebsiteathttp://www.solaredge.us/files/pdfs/application_note_power_
control_configuration.pdf.
l Limit:Theinvertermaximumoutputpower
l Country:Theselectedcountryandgridsetting
l Voltage (Vdc):TheDCinputvoltage
l Temp(°Cor°F):Theinverterheatsinktemperature
Three Phase Inverter with synergy technology Guide MAN-01-00401-1.1
51