Installation Manual
Chapter 5: Activating, Commissioning and
Configuring the System Using SolarEdge
Inverter SetApp
Ifapplicable,youcanconnectcommunicationoptionsatthisstage,asdescribedinSettingUp
Communicationonpage56.
Onceallconnectionsaremade,thesystemshouldbeactivatedandcommissionedusingtheSolarEdge
InverterSetAppmobileapplication.YoucandownloadtheappfromtheiTunesandGooglePlayapp
storespriortoreachingthesite.
Internetconnectionisrequiredforthedownloadandfortheone-timeregistration,howevernot
requiredforusingtheSetApp.
Step 1: Activating the Installation
Duringsystemactivation,aWi-Ficonnectioniscreatedbetweenthemobiledeviceandtheinverterand
thesystemfirmwareisupgraded.
Beforeactivation-download,register(firsttimeonly)andlog-intoSetApponyourmobiledevice.
Internetconnectionisrequiredforthedownloadandfortheone-timeregistration.
To activate the installation:
1. TurnONtheACcircuitbreakeronthemaindistributionpanel.
2. MovetheinverterON/OFF/PswitchtotheONposition.
3. MovetheConnectionUnitDCswitchtotheONposition.
4. OpenSetAppandfollowtheinstructionsonthescreen(scantheinverterbar-code;movethe
ON/OFF/PswitchtoPpositionandreleasewithin5sec.backtoON(1)position).SetAppcreatesaWi-
Ficonnection,upgradestheinverterCPUfirmwareandactivatestheinverter.
5.
Whentheactivationiscomplete,dooneofthefollowing:
l SelectActivate Another Invertertocontinueactivatingadditionalinverters
l SelectStart Commissioningforpairingandothersystemconfiguration.TheCommissioning
screenisdisplayed.Refertothenextsectionformoreinformation.
Three Phase Inverter with synergy technology Guide MAN-01-00401-1.1
37
Chapter 5: Activating, Commissioning and Configuring the System Using SolarEdge