Installation Manual

NOTE
The symbol appears at grounding points on the SolarEdge equipment. This symbol is also used in
this manual.
NOTE
A SolarEdge inverter may be installed in a site with a generator, however must not operate at the same
time as the generator. Operating an inverter and a generator simultaneously will void the warranty.
SolarEdge requires installing a physical or electronic interlock, which will prevent the generator and
inverter from operating simultaneously. Interlock procurement, installation, maintenance and support
are the responsibility of the installer. Damage to the inverter due to incorrect interlock installation or use
of an interlock that is incompatible with the SolarEdge system will render the SolarEdge warranty
invalid.
IMPORTANTSAFETYINFORMATION
l Building or structures with both utility service and a PV system, complying with NEC 690.12, shall
have a permanent plaque or directory including the following wording:PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID SHUTDOWN. The term “PHOTOVOLTAIC” may be replaced with
“PV.The plaque or directory shall be reflective, with all letters capitalized and having a minimum
height of 9.5mm (3/8 in.) in white on red background.
l Attention -The system status indicator shall be installed in a location in close proximity to the
system actuator, where the indication of safe shutdown can be clearly seen.
l This rapid shutdown system is required to be provided with an actuating device or a status
indicator which shall be installed in a location accessible to first responders, or be connected to an
automatic system which initiates rapid shutdown upon the activation of a system disconnect or
activation of another type of emergency system.
l Additionally, in a prominent location near the actuator device the end use installation shall be
provided with a permanent marking including the following wording:PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID SHUTDOWN. The term “PHOTOVOLTAIC” may be replaced with
“PV”. The plaque or directory shall be reflective, with all letters capitalized and having a minimum
height of 9.5mm (3/8 in.) in white on red background.
HANDLING AND SAFETY INSTRUCTIONS
Three Phase Inverter with synergy technology Guide MAN-01-00401-1.1
9