Installation Guide
2. Prepare to connect the RS485 wiring to one of the available RS485 ports of the
device. Note that some inverters have one RS485 port, some have two RS485 ports.
3. Pull out the RS485 connector located on the communication board, as shown in the
figure below.
Figure 16: Inverter RS485 connection
4.
Loosen the screws of RS485 terminal block pins B, A and G of the port you wish to
connect.
Figure 17: RS485 terminal block
5.
Insert the wire ends into the G, A and B pins shown above. Use Four- or six-wire
twisted pair cable for this connection.
You can use any color wire for each of the A, B and G connections, as long as:
The same color wire is used for all A pins the same color for all B pins and the
same color for all G pins
The wire for G is not from the same twisted pair as A or B.
6. Tighten the terminal block screws.
7. Push the RS485 terminal block firmly all the way into the communication board.
8.
If the inverter is at the end of the RS485 bus, terminate by switching a termination
Energy Meter with Modbus Connection MAN-01-00270-1.3
18 Installing and Connecting the Meter