Install Manual
Modbus Communication LEDs
ThecommunicationLEDislocatedattheupperleftcorner.ThefollowingareindicationsoftheLEDlight:
LED
color
Function Indication Troubleshooting
Red
Flashing
An invalid packet: bad baud rate, bad CRC,
noise, bad parity, etc.
Check that the communication wires
are connected correctly.
ON The address is set to zero: an invalid choice
Check that the Device ID is set to 2 in
the RS485 Conf screen.
Flashing with
yellow LED
A possible address conflict (two devices with
the same DIP switch address).
Check that the Device ID is set to 2 in
the RS485 Conf screen.
Yellow Flashing Valid packets addressed to different devices. N/A
Green Flashing A valid packet addressed to this device N/A
SolarEdge SolarEdge Electricity Meter Installation Guide MAN-01-00270-1.0
18