Install Manual

<OK> is not displayed
If<OK>isnotdisplayedintheStatuslineofthestatusscreenshownabove,themeterisnot
communicatingwiththeinverter.Checkthefollowing:
l Therearenolooseconnectionsattheinvertercommunicationboardandatthemeter.
l Thewiringbetweentheblack4-pinterminalblockonthemeterandtheRS485terminalblockonthe
communicationboardiscorrect.
l Checkforwaterdamageorsealingproblems:
o
Inspecttheentireconduitrunforpossiblepointsofwaterpenetration,andfixleaks.
o
Ensurethatproperoutdoorratedcomponentsareused.
An error message is displayed
l IfComm. Errorisdisplayedinthemeterstatusscreen,verifyproperconnectionof:
o
TheRS485cablesandconnectors
o
TheACconnectionofthemeter
l IfError 185 Meter Comm. Errormessageisdisplayed,contactSolarEdgesupport.
Total [Wh] value is not advancing
IftheTotal[Wh]valuedisplaysasteadyvaluealthoughtheinverterisproducingpower,checkthe
following:
l Therearenolooseconnectionsattheinverterconnectorsandatthemeter,specificallytheACwiring
onthemeter10-pinconnector.
l TheCTblackandwhitecablesarecorrectlyconnectedtothe6-pinconnectoronthemeter:
o
WhiteCTwireisconnectedtotheL1/L2whitedot.
o
BlackCTwireisconnectedtotheL1/L2blackdot.
l TheL1/L2cablepassesthroughtheCTinthecorrectdirection(righttoleft),accordingtothearrow
ontheinsideoftheCT.
Figure 16: Meter Connection diagram
l Checkforwaterdamageorsealingproblems:
o
Inspecttheentireconduitrunforpossiblepointsofwaterpenetration,andfixleaks.
o
Ensurethatproperoutdoorratedcomponentsareused.
SolarEdge SolarEdge Electricity Meter Installation Guide MAN-01-00270-1.0
16
<OK> is not displayed