Install Manual
Appendix A: Troubleshooting Meter
Connection
SolarEdgerevenuegradeinvertershaveabuiltinRevenueGradeMeter(RGM).Fortroubleshooting
RGMs,refertohttp://www.solaredge.com/files/pdfs/built-in_rgm_troubleshooting.pdf.Thissection
describeshowtotroubleshootmeter-relatedinstallationandperformanceerrors.
Communication Status Screen Troubleshooting
Thecommunicationstatusscreenshoulddisplaythefollowing:
w w w w w w w w D e v P r o t # #
R S 4 8 5 - 1 < M T R > < W N > < 1 >
R S 4 8 5 - 2 < - - - > < - - > < - - >
Z i g B e e < - - - > < - - > < - - >
Device Type or Protocol are configured incorrectly
IfMTR(meter)isnotdisplayedasthedevicetype(DEV),orWN(WattNode)isnotdisplayedastheProt
(protocol),configurethemeterasfollows.:
1. SelectCommunicationèRS485-x ConfèDevice Typeè Revenue Meter.
2. SelectCommunication è RS485-x Conf è Protocol èWattNode.
3. CheckthattheDeviceIDunderCommunication è RS485-x Conf è Device IDissetto2.
4. SelectRevenue Meter è Meter Func. èExport+Import/Export/Import/Consumption.
Number of devices is not displayed
If<-->isdisplayedunderthe##columnintheCommunicationstatusscreen,themeterisnot
communicatingwiththeinverter.Checkthefollowing:
l Themeterconfigurationisasdescribedabove.
l Therearenolooseconnectionsattheinverterconnectorsandatthemeter,specificallytheRS485
wiring.
l Thewiringbetweentheblack4-pinterminalblockonthemeterandtheRS485terminalblockonthe
communicationboardiscorrect,asshowninFigure 9.
l Checkforwaterdamageorsealingproblems:
o
Inspecttheentireconduitrunforpossiblepointsofwaterpenetration,andfixleaks.
o
Ensurethatproperoutdoorratedcomponentsareused.
l UseaVoltmetertomeasurethevoltageonthemeter10-pinterminalblock.TheL1–L2linetoline
voltageshouldbe208-240Vac.
Meter Status Screen Troubleshooting
P r o d u c t i o n M e t e r
S t a t u s : < O K / E r r o r >
P o w e r [ W ] : x x x x x . x
E n e r g y [ W h ] : x x x x x . x