Install Manual

Chapter 3: SolarEdge Device Configuration
ThissectiondescribesbasicconfigurationofSolarEdgedevices(inverter/CCG)forusingameter.In
addition,configurationspecifictotheapplicationbeingusedisrequiredinsomecases.Refertothe
followingdocuments:
l ExportLimitation-http://www.solaredge.us/files/pdfs/products/export_limitation_application_
note_NA.pdf
l ConsumptionandProductionMonitoring-
http://www.solaredge.us/files/pdfs/products/consumption_production_monitoring_application_
note.pdf
l StorEdgeSmartEnergyManagementoff-gridapplications-
http://www.solaredge.us/files/pdfs/storedge_backup_installation_guide_NA.pdf.
ForconfiguringtwoconnectedmetersrefertoInstalling Two Metersonpage19.
To configure the SolarEdge device:
UsethefouruserbuttonstocontroltheLCDpanelmenus:
l Esc:Goestothebeginningofthecurrentlyenteredparameterortothepreviousmenu.
l Up (1)andDown (2):Movesthecursor(>)totherelevantmenuoption.
l Enter (3):Usedtoselectanoption
1. VerifythatthedeviceON/OFFswitchisOFF.
2.
TurnONtheACswitchofthemaincircuitboard.
WARNING!
ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is
removed.
RISQUE D’ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le couvercle de l'onduleur
est retiré.
3.
PresstheEnter(3)buttonforatleastfiveseconds.Thefollowingmessageisdisplayed:
P l e a s e e n t e r
P a s s w o r d
* * * * * * * *
4. Usethethreerightmostbuttons(Up-1,Down-2andEnter-3)totypeinthefollowingdefault
password:12312312.
5.
ScrolltotheCommunicationmenuandselectRS485-X Conf(XrepresentstheactualRS485portto
whichtheelectricitymeterisconnected:1orEfortheinverter;1or2orEfortheCCG).Thefollowing
screenisdisplayed:
D e v i c e T y p e < S E >
P r o t o c o l < M >
D e v i c e I D < 1 >
S l a v e D e t e c t < # >
S l a v e L i s t < # >
SolarEdge SolarEdge Electricity Meter Installation Guide MAN-01-00270-1.0