P400 Installation
Table Of Contents
- SolarEdge Installation Guide - North America Version 4.0
- Disclaimers
- Support and Contact Information
- Contents
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- Chapter 1: Introducing the SolarEdge Power Harvesting System
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Connecting the AC and the Strings to the Safety Switch
- Chapter 5: Commissioning the Installation
- Chapter 6: User Interface
- Chapter 7: Setting Up Communication
- Appendix A: Errors and Troubleshooting
- Appendix B: Technical Specifications
- Appendix C: Mechanical Specifications
- Appendix D: External Fan Maintenance and Replacement
- Appendix E: Replacing and Adding System Components
- Appendix F: Inverter Arc Detection and Interruption
SE3000A-US SE3800A-US SE5000A-US SE6000A-US SE7600A-US Units
Utility monitoring, islanding protection, country
configurable thresholds
Yes
INPUT
Maximum DC power (Module STC) 4050 5100 6750 8100 10250 W
Transformer-less, ungrounded Yes
Maximum input voltage 500 Vdc
Nominal DC input voltage 350 @240V
325 @208V / 350
@240V
350 @240V
Maximum input current
1
9.5 13
16.5 @208V
15.5 @240V
18 23 Adc
Maximum input short circuit current 45 Adc
Maximum input source back-feed current 0 A
Reverse-polarity protection Yes
Ground-fault isolation detection 600 kΩ Sensitivity
Maximum inverter efficiency 97.7 98.2 98.3 98.3 98 %
CEC weighted efficiency 97.5 98
97.5 @208V
98 @240V
97.5 97.5 %
Night time power consumption < 2.5 W
ADDITIONAL FEATURES
Supported communication interfaces RS485, Ethernet, ZigBee (optional), cellular (optional)