Problem Possible Cause Possible Solution
SafeDC mode was previously
disabled using the SolarEdge Key
Enable the SafeDC using the
SolarEdge Key.
Pairing to the inverter failed The power optimizers are shaded
If you connected the inverter to
the SolarEdge monitoring
portal using one of the
communication options, you
can perform pairing remotely.
Before leaving the site, make
sure that the inverter ON/OFF
switch is ON and S_OK
indication appears on the LCD
to indicate connection to the
monitoring portal.
SolarEdge-Installation Guide MAN-01-00002-4.0
96
Power Optimizer Troubleshooting