P400 Installation
Table Of Contents
- SolarEdge Installation Guide - North America Version 4.0
- Disclaimers
- Support and Contact Information
- Contents
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- Chapter 1: Introducing the SolarEdge Power Harvesting System
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Connecting the AC and the Strings to the Safety Switch
- Chapter 5: Commissioning the Installation
- Chapter 6: User Interface
- Chapter 7: Setting Up Communication
- Appendix A: Errors and Troubleshooting
- Appendix B: Technical Specifications
- Appendix C: Mechanical Specifications
- Appendix D: External Fan Maintenance and Replacement
- Appendix E: Replacing and Adding System Components
- Appendix F: Inverter Arc Detection and Interruption
Verifying the Connection
Afterconnectingandconfiguringacommunicationoption,performthefollowingstepsto
checkthattheconnectiontothemonitoringserverhasbeensuccessfullyestablished.
1. Closetheinvertercover:Attachtheinvertercoverandsecureitbytighteningthescrews
withatorqueof9.0N*m/6.6lb.*ft.Forpropersealing,firsttightenthecornerscrews
andthenthetwocentralscrews(seealsoFigure 30).
2. TurnONtheACtotheinverterbyturningONthecircuitbreakeronthemaindistribution
panelandturningontheSafetySwitch.
3. WaitfortheinvertertoconnecttotheSolarEdgemonitoringportal.Thismaytakeupto
twominutes.
AstatusscreensimilartothefollowingappearsontheLCDpanel:
V a c [ V ] V d c [ V ] P a c [ w ]
2 4 0 . 7 1 4 . 1 0 . 0
P _ O K : 0 0 0 / 0 0 0 < S _ O K >
- - - - - - - - - - - - - - - O F F
S_OK:IndicatesthattheconnectiontotheSolarEdgemonitoringportalissuccessful.IfS_OK
isnotdisplayed,refertoErrors and Troubleshooting on page 83.