P400 Installation
Table Of Contents
- SolarEdge Installation Guide - North America Version 4.0
- Disclaimers
- Support and Contact Information
- Contents
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- Chapter 1: Introducing the SolarEdge Power Harvesting System
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Connecting the AC and the Strings to the Safety Switch
- Chapter 5: Commissioning the Installation
- Chapter 6: User Interface
- Chapter 7: Setting Up Communication
- Appendix A: Errors and Troubleshooting
- Appendix B: Technical Specifications
- Appendix C: Mechanical Specifications
- Appendix D: External Fan Maintenance and Replacement
- Appendix E: Replacing and Adding System Components
- Appendix F: Inverter Arc Detection and Interruption
WARNING!
The inverter must be configured to the proper country in order to ensure that it
complies with the country grid code and functions properly with that country grids.
L'onduleur doit être configuré pour le pays approprié afin d'assurer un
fonctionnement convenable avec le réseau de ce pays.
Alistofcountriesisdisplayed.Ifnocountryisconfigured,thevalueis<NONE>.
NOTE
If an inverter is not configured to any country, it will not produce energy, and the
following message will be displayed on the LCD:
No Country Selected
Aplussign(+)nearthecountryindicatesthatanothermenuwillbedisplayedafter
selection.
l WhenselectingAuto(singlephaseonly),theinverterautomaticallydetectsthe
usedgrid:208VACor240VAC.Whenusingsinglephaseinverters,referto
Supported AC Gridsonpage11todetermineiftheAutooptionmaybeused.
l WhenselectinganoptionwithNo NeutralorNo N,connectiontoNeutrallineis
notrequired.Foranyotheroption,youmustconnecttheNeutralline.
l Whenconnectingtothe480/277Vgrid,selectthe277Vsetting.
2. Confirmyourcountryselectionintheconfirmationscreen:ToggletoYES andpressEnter.
Language
1. SelecttheLanguage optiontosetthelanguageinwhichtheLCDshoulddisplay.
2. Confirmyourlanguageselectionintheconfirmationscreen:ToggletoYESandpress
Enter.
Communication
1. SelecttheCommunication optiontodefineandconfigure:
l Thecommunicationoptionusedbytheinvertertocommunicatewiththe
SolarEdgemonitoringportal
l ThecommunicationoptionusedtocommunicatebetweenmultipleSolarEdge
devicesorotherexternalnon-SolarEdgedevices,suchaselectricitymetersor
loggers.
SolarEdge-Installation Guide MAN-01-00002-4.0