P400 Installation
Table Of Contents
- SolarEdge Installation Guide - North America Version 4.0
- Disclaimers
- Support and Contact Information
- Contents
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- Chapter 1: Introducing the SolarEdge Power Harvesting System
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Connecting the AC and the Strings to the Safety Switch
- Chapter 5: Commissioning the Installation
- Chapter 6: User Interface
- Chapter 7: Setting Up Communication
- Appendix A: Errors and Troubleshooting
- Appendix B: Technical Specifications
- Appendix C: Mechanical Specifications
- Appendix D: External Fan Maintenance and Replacement
- Appendix E: Replacing and Adding System Components
- Appendix F: Inverter Arc Detection and Interruption
RecommendedOCPDsizepergrid(youmayusealargersizethanthatrecommendedbutneverabove60A):
Inverter 208 VAC 240 VAC
SE10000-US 60 A 60 A
SE11400-US --- 60 A
Three Phase Inverters
SE9KUS SE10KUS SE20KUS Units
OUTPUT
Rated AC power output 9000 10000 20000 VA
Maximum AC power output 9000 10000 20000 VA
AC Output Line Connections
4-wire WYE (L1-L2-L3-N)
plus PE or 3 wire Delta
4-wire WYE (L1-L2-L3-
N) plus PE
4-wire WYE (L1-L2-L3-
N) plus PE
AC output voltage minimum-nominal-maximum (L-N)
1
105-120-132.5 244-277-305 244-277-305 Vac
AC output voltage minimum-nominal-maximum (L-L)
1
183-208-229 422.5-480-529 422.5-480-529 Vac
AC frequency min-nom-max
1
59.3 - 60 - 60.5
(with HI country setting 57 - 60 - 60.5)
Hz
Max. continuous output current (per Phase) 25 12 24 A
Max. output fault current and duration 26 / 20 12 / 20 24 / 20 A / mS
Max. back-feed current 0 A
Power factor range 1 (adjustable from -0.8 to +0.8)
GFDI threshold 1 A
1
For other regional settings please contact SolarEdge Support..
Three Phase Inverters
SolarEdge-Installation Guide MAN-01-00002-4.0
104