P400 Installation
Table Of Contents
- SolarEdge Installation Guide - North America Version 4.0
- Disclaimers
- Support and Contact Information
- Contents
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- Chapter 1: Introducing the SolarEdge Power Harvesting System
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Connecting the AC and the Strings to the Safety Switch
- Chapter 5: Commissioning the Installation
- Chapter 6: User Interface
- Chapter 7: Setting Up Communication
- Appendix A: Errors and Troubleshooting
- Appendix B: Technical Specifications
- Appendix C: Mechanical Specifications
- Appendix D: External Fan Maintenance and Replacement
- Appendix E: Replacing and Adding System Components
- Appendix F: Inverter Arc Detection and Interruption
SE10000A-US SE11400A-US Units
Maximum DC power (Module STC) 13500 15350 W
Transformer-less, ungrounded Yes
Maximum input voltage 500 Vdc
Nominal DC input voltage 325 @ 208V / 350@ 240V Vdc
Maximum input current
1
33 @ 208V
30.5 @ 240V
34.5 Adc
Maximum input short circuit current 45 Adc
Maximum input source back-feed current 0 A
Reverse-polarity protection Yes
Ground-fault isolation detection 600kΩ Sensitivity
Maximum inverter efficiency 98 %
CEC weighted efficiency
97@208
97.5@240
97.5 %
Night-time power consumption < 4 W
ADDITIONAL FEATURES
Supported communication interfaces
RS485, Ethernet, ZigBee (optional),
CDMA (optional)
Revenue Grade Data, ANSI C12.1 Optional
2
1
A higher current source may be used; the inverter will limit its input current to the values stated.
2
Revenue grade inverter P/N: SExxxxA-USxxxxxR2
Single Phase 10-11.4kW Inverters
SolarEdge-Installation Guide MAN-01-00002-4.0
102