P400 Installation
Table Of Contents
- SolarEdge Installation Guide - North America Version 4.0
- Disclaimers
- Support and Contact Information
- Contents
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- Chapter 1: Introducing the SolarEdge Power Harvesting System
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Connecting the AC and the Strings to the Safety Switch
- Chapter 5: Commissioning the Installation
- Chapter 6: User Interface
- Chapter 7: Setting Up Communication
- Appendix A: Errors and Troubleshooting
- Appendix B: Technical Specifications
- Appendix C: Mechanical Specifications
- Appendix D: External Fan Maintenance and Replacement
- Appendix E: Replacing and Adding System Components
- Appendix F: Inverter Arc Detection and Interruption
SE3000A-US SE3800A-US SE5000A-US SE6000A-US SE7600A-US Units
Revenue Grade Data, ANSI C12.1 Optional
1
Rapid Shutdown – NEC 2014 690.12 Functionality enabled when SolarEdge rapid shutdown kit is installed
2
STANDARD COMPLIANCE
Safety UL1741, UL1699B, UL1998, CSA 22.2
Grid connection standards IEEE1547
Emissions FCC part15 class B
RoHS Yes
INSTALLATION SPECIFICATIONS
AC output conduit size / AWG range ¾” minimum / 16-6 AWG
DC input conduit size / # of strings / AWG
range
¾” minimum / 1-2 strings / 16-6 AWG
Dimensions (H x W x D)
21 x 12.5 x 7.2 /
540 x 315x 184
in/mm
Dimensions (H x W x D) with Safety Switch
30.5 x 12.5 x 7.2 /
775 x 315 x 184
in/mm
Weight 44.7 / 20.2 47.7/21.7 lb/kg
Weight with Safety Switch 51.2/ 23.2 54.7/24.7 lb/kg
1
Revenue grade inverter P/N: SExxxxA-US000NNR2 (for SE7600 inverter: US002NNR2)
2
Rapid shutdown kit P/N: SE1000-RSD-S1
Appendix B: Technical Specifications
SolarEdge-Installation Guide MAN-01-00002-4.0
99