NOTE
For single-phase inverters, use only copper conductors rated for a minimum of
75°C/167°F. For three-phase inverters, use only copper conductors rated for a minimum
of 90°C/194°F. For three-phase inverters where opposite polarity DC conductors are
routed in the same conduit, 1000V rated cables must be used.
NOTE
This inverter is provided with an IMI (Isolation Monitor Interrupter) for ground fault
protection.
NOTE
The symbol appears at grounding points on the SolarEdge equipment. This symbol is
also used in this manual.
IMPORTANT SAFETY INSTRUCTIONS
SolarEdge-Installation Guide MAN-01-00002-4.0
9