Specifications
© SolarEdge Technologies Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc.
All other trademarks mentioned herein are trademarks of their respective owners. Date: 07/2020/V02/ENG NAM. Subject to change without notice.
(6) For detailed ring sizing information refer to: http://www.solaredge.com/sites/default/les/ring_sizing_na.pdf
(7) It is not allowed to mix P405/P485/P505 with P320/P340/P370/P400/P401 in one ring
(8) A ring with more than 30 optimizers does not meet NEC rapid shutdown requirements; safety voltage will be above the 30V requirement
(9) For 208V grid: it is allowed to inall up to 7,200W per ring when the maximum power difference between each ring is 1,000W
(10) For 277/480V grid: it is allowed to inall up to 15,000W per ring when the maximum power difference between each ring is 2,000W
Power Optimizer
For North America
P320 / P340 / P370 / P400 / P401 / P405 / P485 / P505
Optimizer model
(typical module
compatibility)
P320
(for 60-cell
modules)
P340
(for high-
power
60-cell
modules)
P370
(for higher-
power
60 and 72-
cell
modules)
P400
(for 72 &
96-cell
modules)
P401
(for high
power 60
and 72 cell
modules)
P405
(for high-
voltage
modules)
P485
(for high-
voltage
modules)
P505
(for higher
current
modules)
INPUT
Rated Input DC Power
(1)
320 340 370 400 405 485 505 W
Absolute Maximum Input Voltage
(Voc at lowe temperature)
48 60 80 60 125
(2)
83
(2)
Vdc
MPPT Operating Range 8 - 48 8 - 60 8 - 80 8-60 12.5 - 105 12.5 - 83 Vdc
Maximum Short Circuit Current
(Isc)
11 10.1 11.75 11 14 Adc
Maximum Eciency 99.5 %
Weighted Eciency 98.8 98.6 %
Overvoltage Category II
OUTPUT DURING OPERATION
(
POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER
)
Maximum Output Current 15 Adc
Maximum Output Voltage 60 85 Vdc
OUTPUT DURING STANDBY
(
POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF
)
Safety Output Voltage per Power
Optimizer
1 ± 0.1 Vdc
STANDARD COMPLIANCE
EMC FCC Part15 Class B, IEC61000-6-2, IEC61000-6-3
Safety IEC62109-1 (class II safety), UL1741
Material UL94 V-0 , UV Resiant
RoHS Ye s
INSTALLATION SPECIFICATIONS
Maximum Allowed Syem
Voltage
1000 Vdc
Compatible inverters All SolarEdge Single Phase and Three Phase inverters
Dimensions (W x L x H) 129 x 153 x 27.5 / 5.1 x 6 x 1.1
129 x 153 x 33.5
/ 5.1 x 6 x 1.3
129 x 153 x 29.5
/5.1 x 6 x 1.16
129 x 159 x 49.5 / 5.1 x 6.3 x 1.9
129 x 162 x 59 /
5.1 x 6.4 x 2.3
mm
/ in
Weight (including cables) 630 / 1.4 750 / 1.7 655 / 1.5 845 / 1.9 1064 / 2.3 gr / lb
Input Connector MC4
(3)
Single or dual
MC4
(3)(4)
MC4
(3)
Input Wire Length 0.16 / 0.52 m / ft
Output Wire Type / Connector Double Insulated / MC4
Output Wire Length 0.9 / 2.95 1.2 / 3.9 m / ft
Operating Temperature Range
(5)
-40 - +85 / -40 - +185 ˚C / ˚F
Protection Rating IP68 / NEMA6P
Relative Humidity 0 - 100 %
(1) Rated power of the module at STC will not exceed the optimizer “Rated Input DC Power”. Modules with up to +5% power tolerance are allowed
(2) NEC 2017 requires max input voltage be not more than 80V
(3) For other connector types please contact SolarEdge
(4) For dual version for parallel connection of two modules use P485-4NMDMRM. In the case of an odd number of PV modules in one ring, inalling one P485 dual version power optimizer connected
to one PV module. When connecting a single module seal the unused input connectors with the supplied pair of seals.
(5) For ambient temperature above +85°C / +185°F power de-rating is applied. Refer to Power Optimizers Temperature De-Rating Technical Note for more details.
PV System Design Using
a SolarEdge Inverter
(6)(7)
Single Phase
HD-Wave
Single phase
Three Phase for
208V grid
Three Phase for
277/480V grid
Minimum String Length
(Power Optimizers)
P320, P340, P370,
P400, P401
8 10 18
P405, P485, P505 6 8 14
Maximum String Length (Power Optimizers) 25 25 50
(8)
Maximum Power per String
5700 (6000 with
SE7600-US - SE11400-
US)
5250 6000
(9)
12750
(10)
W
Parallel Strings of Different Lengths or Orientations Ye s