P860 Power Optimizer - North America

Power Optimizer For North America
P860 / P960 / P1101
Power OptimizerModel
(Typical Module Compatibility)
P860
(for 2 x 72 cell modules)
P960
(for 2 x 72 cell modules)
P1101
(for up to 2 x high power or bi-
facial modules)
(1) Rated power of the module at STC will not exceed the Power Optimizer “Rated Input DC Power”. Modules with up to +5% power
tolerance are allowed
(2) In the event of an odd number of PV modules in one string, installation of one P860 /P960 Power Optimizer connected to one PV module is allowed. When connecting a single module to the P860/
P960, seal the unused input connectors with the supplied pair of seals
(3) For other connector types please refer to: https://www.solaredge.com/sites/default/files/optimizer-input-connector-compatibility.pdf
(4) For ambient temperature above +70˚C / +158˚F, power de-rating is applied. Refer to the Power Optimizers Temperature De-Rating Application Note for more details
PV System Design Using a
SolarEdge Inverter
(5)(6)
208V Grid
SE14.4K*
208V Grid
SE17.3K*
277/480V Grid
SE20K, 30K
277/480V Grid
SE33.3K*, SE40K*
Compatible Power Optimizers P860, P960, P1101 P860, P960, P1101 P860, P960, P1101 P860, P960, P1101
Minimum String
Length
Power Optimizers
8 10 14 14
PV Modules
15 19 27
27
Maximum String
Length
Power Optimizers
30 30 30
30
PV Modules
60 60 60 60
Maximum Continuous Power per String
7200 8820 15300 15300
W
Maximum Allowed Connected Power per String
(7)
(Permitted only when the difference in connected
power between strings is up to 2,000W for the
277/480V grid, or 1,000W for the 208V grid)
1 string - 8400 1 string - 10020 1 string - 17550
2 strings or
less - 17550
W
2 strings or
more - 9000
2 strings or
more - 10620
2 strings or
more - 20300
3 strings or
more - 20300
Parallel Strings of Different Lengths or Orientations Yes
* The same rules apply for Synergy units of equivalent power ratings, that are part of the modular Synergy Technology inverter
(5) P860/P960 can be mixed in one string only with P860/P960
INPUT
Rated Input DC Power
(1)
860
960
1100
W
Connection Method
Single input for series connected modules
Absolute Maximum Input Voltage
(Voc at lowest temperature)
60 125
Vdc
MPPT Operating Range
12.5 - 105
Vdc
Maximum Short Circuit Current (Isc)
22
23.2
Adc
Maximum Short Circuit Current per Input (Isc)
11
11.6
14.1
Adc
Maximum Efficiency
99.5
%
Weighted Efficiency
98.6
%
Overvoltage Category
II
OUTPUT DURING OPERATION
(
POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER
)
Maximum Output Current
18
Adc
Maximum Output Voltage
80
Vdc
OUTPUT DURING STANDBY
(
POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF
)
Safety Output Voltage per Power Optimizer
1 ± 0.1
Vdc
STANDARD COMPLIANCE
Photovoltaic Rapid Shutdown System
Compliant with NEC 2014, 2017, 2020
EMC
FCC Part 15 Class A, IEC61000-6-2, IEC61000-6-3
Safety
IEC62109-1 (class II safety), UL1741
Material
UL94 V-0, UV resistant
RoHS
Yes
INSTALLATION SPECIFICATIONS
Compatible SolarEdge Inverters
Three phase inverters
SE30K & larger
Maximum Allowed System Voltage
1000
Vdc
Dimensions (W x L x H)
129 x 169 x 59 / 5.1 x 6.65 x 2.32
129 x 162 x 59 / 5.1 x 6.4 x 2.32
mm / in
Weight
1064 / 2.34
gr / lb
Input Connector
MC4
(3)
Input Wire Length Options
Input #1
Input #2
Input #1
Input #2
-
m / ft
1
(-) 0.16 / 0.52,
(+) 0.16 / 0.52
(-) 0.16 / 0.52,
(+) 0.16 / 0.52
(-) 1.6 / 5.2,
(+) 1.6 / 5.2
(-) 1.6 / 5.2,
(+) 1.6 / 5.2
1.6 / 5.2
2
(-) 1.6 / 5.2,
(+) 0.16 / 0.52
(-) 0.16 / 0.52,
(+) 1.6 / 5.2
3
(-) 1.6 / 5.2,
(+) 1.6 / 5.2
(-) 1.6 / 5.2,
(+) 1.6 / 5.2
Output Wire Type / Connector
Double insulated; MC4
Output Wire Length
2.3 / 7.5
2.3 / 7.5
2.4 / 7.8
m / ft
Operating Temperature Range
(4)
-40 to +85 / -40 to +185
˚C / ˚F
Protection Rating
IP68 / NEMA6P
Relative Humidity
0 - 100
%
© SolarEdge Technologies Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Ltd.
All other trademarks mentioned herein are trademarks of their respective owners. Date: 10/2021 DS-000013-4.3-NA. Subject to change without notice.
-
IEC62109-1 (class II safety), UL1741, UL3741
129 x 169 x 72 / 5.1 x 6.65 x 2.83
1410 / 3.1 1340 / 2.95
(6) P860/P960 design with three phase 208V inverters is limited. Use the SolarEdge Designer for verification
(7) To connect more STC power per string, design your project using SolarEdge Designer