P700 / P730 Commercial Frame Mounted Power Optimizers - North America
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE 
are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are 
trademarks of their respective owners. Date: 10/2017 V.01. Subject to change without notice.
P700 
P730 
INPUT
RatedInputDCPower
(1)
700 730 W
AbsoluteMaximumInputVoltage 
(Vocatlowesttemperature)
125 Vdc
MPPTOperangRange 12.5-105 Vdc
MaximumShortCircuitCurrent(Isc) 10.1 11 Adc
MaximumDCInputCurrent 12.63 13.75 Adc
MaximumEciency 99.5 %
WeightedEciency 98.6 %
OvervoltageCategory II
MaximumOutputCurrent 15 Adc
MaximumOutputVoltage 85 Vdc
SafetyOutputVoltageperPowerOpmizer 1±0.1 Vdc
EMC FCCPart15ClassB,IEC61000-6-2,IEC61000-6-3
Safety IEC62109-1(classIIsafety),UL1741
RoHS Yes 
CompableSolarEdgeInverters Threephaseinverters
MaximumAllowedSystemVoltage 1000 Vdc
Dimensions(WxLxH) 139x165x63\5.5x6.5x2.5 mm/in
Weight(includingcables) 1185/2.6 gr/lb
InputConnector MC4Compable
OutputWireType/Connector DoubleInsulated;MC4Compable
OutputWireLength 2.1/6.9 m/
OperangTemperatureRange
(2)
-40-+85/-40-+185 ˚C/˚F
ProteconRang IP68/NEMA6P
RelaveHumidity 0-100 %
SolarEdge Power Optimizer Module Add-On
For Commercial Installations for North America P700 / P730 
 
MinimumStringLength 
(PowerOpmizers)
8 13
MaximumStringLength 
(PowerOpmizers)
30 30
MaximumPowerperString 6000
(6)
12750
(7)
W
ParallelStringsofDierentLengths 
orOrientaons
Yes  
Supportedframe
cross-section
1.1-2.4mm/0.04-0.094in
>12mm/0.48in
(1)
RatedcombinedSTCpowerof2modulesconnectedinseries.Moduleofupto+5%powertoleranceallowed.
2)
Forambienttemperatureabove+70˚C/+158˚Fpowerde-ratingisapplied.RefertoPowerOptimizersTemperatureDe-RatingApplicationNoteformoredetails.
(3)
P600,P700andP730canbemixedinonestring.ItisnotallowedtomixP600/P700/P730withP300/P320/P400/P405inonestring.
(4)
InacaseofoddnumberofPVModulesinonestringitisallowedtoinstalloneP700/P730poweroptimizerconnectedtoonePVModule.
(5)
P700andP730designwiththreephase208Vinvertersislimited.UsetheSolarEdgeSiteDesignerforverification.
(6)
ForSE14.4KUS-208:Itisallowedtoinstallupto6,500Wperstringwhen3stringsareconnectedtotheinverterandwhenthemaximumpowerdifferencebetweenthestringsisupto1,000W.
(7)
ForSE33.3KUS:Itisallowedtoinstallupto15,000Wperstringwhen3stringsareconnectedtotheinverterandwhenthemaximumpowerdifferencebetweenthestringsisupto2,000W.