StorEdge Backup Interface Specs
Backup Interface for North America
BI-EUSGN-01 / BI-NUSGN-01
BI-EUSGN-01 BI-NUSGN-01
INPUT FROM GRID
AC Current Input 200 A
AC Output Voltage (Nominal) 240 Vac
AC Output Voltage Range 211 - 264 Vac
AC Frequency (Nominal) 60 Hz
AC Frequency Range 59.3 - 60.5 Hz
Microgrid Interconnection Device Rated Current 200 A
Service Side AC Main Circuit Breaker Rated Current 200 N/A A
Service Side AC Main Circuit Breaker Interrupt Current 10k N/A A
Grid Disconnection Switchover Time <100 ms
OUTPUT TO MAIN DISTRIBUTION PANEL
Maximum AC Current Output 200 A
AC L-L Output Voltage (Nominal) 240 Vac
AC L-L Output Voltage Range 211 - 264 Vac
AC Frequency (Nominal) 60 Hz
AC Frequency Range 59.3 - 60.5 Hz
Maximum Inverters AC Current Output in Backup Operation 78 A
Imbalance Compensation in Backup Operation 5000 W
AC L-N Output Voltage in Backup (Nominal) 120 V
AC L-N Output Voltage Range in Backup 105 - 132 V
AC Frequency Range in Backup 55 - 65 Hz
INPUT FROM INVERTER
Number of Inverter Inputs 3 #
Rated AC Power 7,600 W
Maximum Continuous Input Current @ 240V 32 A
Rated AC Power in Continuous Backup Operation 6,100 W
Maximum Continuous Input Current in Backup Operation 26 A
Peak AC Power (<10 sec) in Backup Operation 7,000 W
Peak AC Current (<10 sec) in Backup Operation 30 A
Inverter Input AC Circuit Breaker 40 A
Upgradability Up to 3 X 40A CB
(1)
GENERATOR
(
2
)
Maximum Rated AC Power 15,000 W
Maximum Continuous Input Current 63 Adc
Dry Contact Switch Voltage Rating 250/30 Vac/Vdc
Dry Contact Switch Current Rating 5 A
2-wire Start Switch Ye s
ADDITIONAL FEATURES
Inallation Type Suitable for use as service equipment For main lug only
Number of Communication Inputs 2
Communication RS485
Energy Meter (for Import/Export) 1% accuracy
Manual Control Over Microgrid Interconnection Device Ye s
(1)
Each 40A CB supports an 7600W inverter; CB upgrade kit is available with the following part numbers: for 40A CB CB-UPG-40-01
(2)
Requires supporting inverter rmware