4.3 Installation materials
Following installation materials should be prepared by installers.
Power cable
Data cable
Ground wire
Bipolar external isolator, when two or more battery systems in parallel, each of
them shall have a bipolar isolator.
NOTICE
Make sure that the cross-sectional area of charging cables is 25 to 35
mm
2
.
A breaker between CFE battery and inverter was recommended to
install, and the breaker’s min. current should be over 150A or following
with local regulations.
4.4 Tools
To install the battery pack, those following tools are probably required:
Phillips screwdriver
Torque wrench
Cable crimper
Wire clamp
Voltmeter
Tape measure
Drill
Flat-head screwdriver
In order to protect operator and installer’s safety, please select and use suitable
tools and measuring instruments that are certified for precision and accuracy.
4.5 Safety instruments
When dealing with the battery, following safety gears should be equipped. Installers
must meet the relevant requirements of IEC 60364 or the domestic legislation and
other relevant international standards.