Specifications

L16RE-A_TRJNRE_DS_0315
L16RE-A DATA SHEET
PREMIUM LINE
for Renewable Energy / Hybrid Systems / Backup Power Applications
Page 1 of 2
MODEL: L16RE-A with Bayonet Cap
DIMENSIONS: inches (mm)
BATTERY: Flooded/wet lead-acid battery
COLOR: Maroon (case/cover)
MATERIAL: Polypropylene
* Polyon™ Case
PRODUCT SPECIFICATIONS
BCI
GROUP
SIZE
TYPE
CAPACITY
A
Amp-Hours (AH)
ENERGY
(kWh)
VOLTAGE
TERMINAL
Type
D
DIMENSIONS
B
Inches (mm)
WEIGHT
lbs. (kg)
2-Hr
Rate
5-Hr
Rate
10-Hr
Rate
20-Hr
Rate
48-Hr
Rate
72-Hr
Rate
100-Hr
Rate
100-Hr
Rate
Length Width
Height
C
PREMIUM LINE - DEEP- CYCLE FLOODED BATTERIES
903 L16RE-A* 211 267 299 325 346 354 360 2.16 6 VOLT 5 11.67 (296) 6.95 (177) 17.56 (446) 115 (52)
OPERATIONAL DATA
OPERATING TEMPERATURE SPECIFIC GRAVITY
-4°F to 113°F (-20°C to +45°C). At temperatures
below 32°F (0°C) maintain a state of charge
greater than 60%.
The specific gravity
at 100% state-of-
charge is 1.280
CHARGING INSTRUCTIONS
Do not install or charge batteries in a sealed or non-ventilated compartment. Constant under or
overcharging will damage the battery and shorten its life as with any battery.
CHARGER VOLTAGE SETTINGS (AT 77°F/25°C)
Voltage per cell
Absorption charge 2.35-2.45
Float charge 2.20
Equalize charge 2.58
EXPECTED LIFE VS. TEMPERATURE
Chemical reactions internal to the battery are driven by voltage and temperature. The higher the battery temperature, the faster chemical reactions will
occur. While higher temperatures can provide improved discharge performance the increased rate of chemical reactions will result in a corresponding loss of
battery life. As a rule of thumb, for every 10°C increase in temperature the reaction rate doubles. Thus, a month of operation at 35°C is equivalent in battery
life to two months at 25°C. Heat is an enemy of all lead acid batteries, FLA, AGM and gel alike and even small increases in temperature will have a major
influence on battery life.
Made in the USA
CHARGING TEMPERATURE COMPENSATION
To the Voltage Reading -- Subtract 0.005 volt per cell (VPC) for every 1°C above 25°C or add 0.005 volt per cell for every 1°C below 25°C.
Premium Line batteries manufactured prior to March 2012 have 1.260 SG value.
TERMINAL CONFIGURATIONS
5 LT L-Terminal
Terminal Height Inches (mm)
1.75 (44)
Torque Values in-lb (Nm)
95 – 105 (11 – 12)
Bolt
5/16"
Now Available With
SMART CARBON
Deep-cycle batteries used in off-grid and unstable grid applications are heavily cycled at partial state of charge (PSOC). Operating at PSOC on a regular basis
can quickly diminish the overall life of a battery, which results in frequent and costly battery replacements.
To address the impact of PSOC on deep-cycle batteries in renewable energy (RE), inverter backup and telecom applications, Trojan Battery has now included
Smart Carbon™ as a standard feature in its Industrial and Premium flooded battery lines.

Summary of content (2 pages)