SA-12K Install Guide and Owner Manual
Table Of Contents
- Spec Sheet
 - Wiring Diagrams
 - GUI Screens
 - Physical Installation
- Inverter Components
 - Deciding Backup Circuits
 - Single System Installs
 - Mounting the Sol-Ark
 - Integrating Batteries (Sol-Ark POWERED "OFF")
 - E.M.P Systems Only
 - Connecting Solar Panels
 - Integrating a Generator
 - Integrating Sensors and Accessory Placement
- Battery Temperature Sensor
 - Limiter Sensors (CT Sensors)
 - GEN Start Signal (Two-Wire)
 - CANbus & RS485
 - Wi-Fi Antenna (Dongle)
 - Emergency Stop Signal & PV Rapid Shutdown Signal
 - Misc. Hardware Recommendations
 - Check the voltage on each PV input circuit
 - Check Grid Input Voltage
 - Check Battery Voltage
 - Provide Power to Sol-Ark
 - Indicator LED's
 
 
 - Power Cycle Sequence
 - Wi-Fi / Internet Connection
 - Programming Guide
 - Limiter Sensors (CT Sensors)
 - Install Tips
 - Batteries
 - Parallel Systems
 - Troubleshooting Guide
- LCD is not powering on
 - Panels are connected, but DC Light is not on
 - Panels are not producing
 - Panels are not producing much power
 - The system does not keep batteries charged
 - Auto Gen-Start not working
 - Normal LED isn't on
 - The alarm light is on
 - Grid HM value is negative when it should be positive (only applies in limited home mode)
 - AC Overload Fault or Bus Unbalance Fault
 - The system connects to grid and quickly disconnects
 - DC Overload Fault
 - System is beeping
 - Battery cable sparks when connected
 - Battery symbol on the home screen is red
 - Battery symbol on the home screen is yellow
 - Grid symbol on the home screen is yellow
 - System has restarted
 - Batteries were connected backward
 - Why is the LCD screen still on when the power button is off?
 - The Batt % meter is not reaching 100%
 - Generator setup is reading 0Hz
 - Color Touchscreen is Frozen
 - Consant F18 Faults while powering loads within specification
 - Troubleshooting Phasing Issues
 - Sol-Ark 12K Error Codes
 
 - Install Verification Checklist
 - Sol-Ark 12K Limited Warranty
 
 June 30
th
, 2022          51 
Troubleshooting Phasing Issues 
If the Sol-Ark screen shows Grid Phase Wrong there is a phasing issue with your wiring and it may cause overload faults 
(F18, F26, F34) even with the Load breaker off and WILL CAUSE DAMAGE if left unchecked.  
Single Sol-Ark: To locate the improperly wired phases, measure L1 to L1 (Top Screws) between the Grid and Load 
breaker; you should see 0V AC. Repeat for L2 to L2 between the Grid and Load breaker. Attempt to correct the wiring 
until you are only reading 0V AC between L1 to L1 & L2 to L2. 
Parallel inverters: measure L1 of the Grid breaker to L1 of another unit's Grid breaker; you should see 0V AC. If in 208V 
parallel, measure the lines of the same wire color between sol-arks to see if you read 0V AC. 
Make sure to correct both the Grid and Load wiring; they both need to be correct. 
If the error persists, you will need to check your AC wiring beyond the inverter and may also need to verify that the 
phases are properly labeled coming from your meter. 
Remainder of Page Left Intentionally Blank 