17. ANNEX C
FTP CONFIGURATION
Measurement logs (see “4.2.2. Introduction to DIRIS Digiware M-70”, page 9) can be automatically exported via FTP(S).
17.1. FTP server activation:
Connect to the web server and go to the “Protocols” menu:
Click on “Data Push”.
Authenticationpart:
Site Name & Server Name: used to identify from which DIRIS Digiware M-50/M-70 the les are being exported.
The default site name is “SITE” (must be modied if the exoirt mode is set to EMS) et the default server name
corresponds to the NET ID marked on the front face of the M-50/M-70 gateway.