The way the OID is assigned to a device (instance number) is the following:
OID = Main OID (= default 100) + ModbusAddress:
Device with Main OID (100) is the DIRIS Digiware M-50 / M-70 gateway itself.
The device with OID (1xx) is the device with the Modbus address xx.
Analog Input Object:
The DIRIS Digiware M-50 / M-70 acts as a BACnet gateway. It provides a number of Analog Input objects which may
be available from the devices compatible and connected to the DIRIS Digiware M-50 / M-70.
Whether a device supports an AI object depends on its measurement functionalities.
Ex:
The OID for THD_I1 will return 0 for a DIRIS Digiware I-30 module because this parameter is not handled.
The AI object denes 25 properties. The devices compatible and connected downstream the DIRIS Digiware M-50 /
M-70 support the following properties:
Property BACnet
Object_Identifier Required
Object_Name Required
Object_Type Required
Present_Value Required
Status_Flags Required
Event_State Required
Out_Of_Service Required
Units Required
Description Optional
Reliability Optional
Min_Pres_Value Optional
Minimum_Value_
Timestamp
Optional
Max_Pres_Value Optional
Maximum_Value_
Timestamp
Optional
Average_Value Optional
Instantaneous_Timestamp Proprietary
Average_Timestamp Proprietary
Max_Average_Value Proprietary
Max_Average_Timestamp Proprietary
Min_Average_Value Proprietary
Min_Average_Timestamp Proprietary
Harmonics_Row_02 Proprietary
Harmonics_Row_03 Proprietary
Harmonics_Row_04 Proprietary
Harmonics_Row_05 Proprietary
Harmonics_Row_06 Proprietary
Harmonics_Row_07 Proprietary
Harmonics_Row_08 Proprietary
Harmonics_Row_09 Proprietary
Harmonics_Row_10 Proprietary