Users Manual Part 2
52 EN
DIRIS Digiware D-50 & D-70 - 548088C - SOCOMEC
13. DIRIS DIGIWARE D-50/D-70 TECHNICAL CHARACTERISTICS
13.1. Mechanical characteristics
Type of screen Capacitive touch-screen technology, 10 keys
Screen resolution 350 x 160 pixels
Front panel protection index IP65* (IEC 60529)
Weight DIRIS Digiware D-50 / D-70
210 g
* Front face only. The use of a silicone seal may be required to ensure sufcient sealing of the junction between D-50/D-70 display and
panel door.
13.2. Communication characteristics
Type of screen Multipoint remote screen
Ethernet RJ45 10/100 Mbs Gateway function:
- Modbus TCP (max. 16 simultaneous connections)
- WEBVIEW-M embedded web server (D-70 only)
- BACnet IP
- SNMP v1, v2 & v3
SNTP protocol Updates the screen from an SNTP server.
The display updates the connected devices.
SMTP(S) protocol Sends email notifications from the display.
FTP(S) protocol
Only available with DIRIS Digiware D-70
Automatically exports data via FTP standard or secure server (consumption
curves, load curves, measurement logs)
RJ45 Digiware Control and power supply interface function
RS485 2-3 wires Modbus RTU master communication function
USB Upgrade and configuration via type B micro USB connector
Bluetooth Low Energy (only with DIRIS Digiware D-50/D-70 BLE versions)
Use Visualisation of data from Socomec Bluetooth sensors
Operating frequency 2402 to 2480 MHz
EIRP Power EIRP Power for CE: 6.23 dBm (measured max average)
Max. Power for FCC/IC 3.15 dBm
13.3. Wireless Characteristics
13.3.1. Canada
This device complies with ISED’s licence-exempt RSSs. Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation. Le présent appareil est conforme aux CNR d’ ISED applicables aux
appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes : (1) le dispositif ne doit
pas produire de brouillage préjudiciable, et (2) ce dispositif doit accepter tout brouillage reçu, y compris un brouillage
susceptible de provoquer un fonctionnement indésirable.
Radiation Exposure Statement:
This equipment complies with ISED radiation exposure limits set forth for an uncontrolled environment. This equipment
should be installed and operated with greater than 20cm between the radiator & your body.
Déclaration d’exposition aux radiations:
Cet équipement est conforme aux limites d’exposition aux rayonnements ISED établies pour un environnement non
contrôlé. Cet équipement doit être installé et utilisé à plus de 20 cm entre le radiateur et votre corps.