Users Manual Part 1
8 EN
DIRIS Digiware D-50 & D-70 - 548088C - SOCOMEC
5. INTRODUCTION
5.1. Range
DIRIS Digiware D-50
Multipoint display
Ref. 48290204
DIRIS Digiware D-50 BLE
Multi-point display with
Bluetooth Low Energy
Ref. 4829 0206
DIRIS Digiware D-70
Multipoint display
Ref. 48290203
DIRIS Digiware D-70 BLE
Multi-point display with
Bluetooth Low Energy
Ref. 4829 0207
Ethernet output
Modbus TCP
BACnet IP
SNMP v1, v2 & v3
Ethernet output
Modbus TCP
BACnet IP
SNMP v1, v2, v3
Bluetooth Low Energy
Ethernet output
Modbus TCP
BACnet IP
SNMP v1, v2 & v3
Ethernet output
Modbus TCP
BACnet IP
SNMP v1, v2, v3
Bluetooth Low Energy
- -
WEBVIEW-M embedded
web server Power & Energy
Monitoring
WEBVIEW-M embedded
web server Power & Energy
Monitoring
5.2. Introduction to DIRIS Digiware D
DIRIS Digiware D-50 and D-70 are system displays and act as the unique point of access to measurements fromDIRIS
Digiware modules.
They can also display measurements from other SOCOMEC meters and measuring devices: COUNTIS, DIRISA, DIRISB.
They centralise data from up to 32 devices (a maximum of 192 circuits).
These products may be connected by a Digiware bus and/or an RS485 bus.
Centralised products can be shown as well as congured by DIRIS Digiware D displays.
5.2.1. Introduction to DIRISDigiware D-50
The DIRIS Digiware D-50 display is a master on the Digiware bus and acts as a gateway interface to communicate
measurements over RS485 and Ethernet.
The RS485 port can be congured as a Master or Slave.
The Ethernet port is used to:
• Communicate via Modbus TCP (max. 16 simultaneous connections), measurements from meters and measuring
devices connected to the Digiware and RS485 buses.
• Communicate via BACnet IP and SNMP, measurements from meters and measuring devices connected to the
Digiware and RS485 buses.
• Automatically send alarm notications via emails (SMTPS).
• Synchronize the date/time to an SNTP server.
• Automatically and cyclically export historical measurements via FTPS.