Users Manual Part 1
30 EN
DIRIS Digiware D-50 & D-70 - 548088C - SOCOMEC
8.3.2.2. Changing the load settings
Following the example above, to change the settings, press "OK".
LOAD
|
I-30@4 ID:FOC1D2
INPUT I01 I02 I03
CT 250 A 250 A 250 A
WAY +/DIRECT +/DIRECT +/DIRECT
LINE V V3 V2 V1
LOAD L1 L1 L1
TYPE 3P+N_3CT
3P+N_3CT 3P+N_3CT
PRESS OK TO ENTER SETTINGS
You can change each parameter to congure each of the loads (the values in bold are shown on the screen in
theexample below)
• LOAD -> congure load 1: L1 - load 2: L2 - load 3: L3
• NAME -> name of the load: LOAD 1 (edit with max. 16 characters)
• TYPE -> type of load: single-phase (1P+N), two-phase (2P), three-phase (3P), three-phase+neutral (3P+N)
• NOMINAL I (A) -> set the nominal current of the load: 20A (caution: the nominal current of the load may differ from the
rating of the current sensor (CT1) used: a 63A current sensor can be used to monitor a 20A circuit breaker.
• CT1 -> current measured by the current sensor connected to input: I01, I02, I03.
LOAD
|
I-30@4 ID:FOC1D2
LOAD
L1
NAME LOAD 1
TYPE 3P+N_3CT
NOMINAL I (A) 00020
CT1 I01
…
Go to "CT settings" to perform the conguration of current sensors.
LOAD
|
I-30@4 ID:FOC1D2
…
NAME LOAD 1
TYPE 3P+N_3CT
NOMINAL I (A) 00020
CT1 I01
CT settings
…
Congure:
• WAY -> Direction of the current sensor +/DIRECT, -/INV.
• V Line -> V1, V2, V3 (position of the current sensor on phase 1, phase 2 or phase 3).
• CT -> Indicates the rating of the current sensor used. Click on “DETECT” to automatically detect the rating. After2
seconds, the rating is displayed.
Complete the process by selecting "OK" then "OK" again