Users Manual Part 1

30 EN
DIRIS Digiware D-50 & D-70 - 548088C - SOCOMEC
8.3.2.2. Changing the load settings
Following the example above, to change the settings, press "OK".
LOAD
|
I-30@4 ID:FOC1D2
INPUT I01 I02 I03
CT 250 A 250 A 250 A
WAY +/DIRECT +/DIRECT +/DIRECT
LINE V V3 V2 V1
LOAD L1 L1 L1
TYPE 3P+N_3CT
3P+N_3CT 3P+N_3CT
PRESS OK TO ENTER SETTINGS
You can change each parameter to congure each of the loads (the values in bold are shown on the screen in
theexample below)
LOAD -> congure load 1: L1 - load 2: L2 - load 3: L3
NAME -> name of the load: LOAD 1 (edit with max. 16 characters)
TYPE -> type of load: single-phase (1P+N), two-phase (2P), three-phase (3P), three-phase+neutral (3P+N)
NOMINAL I (A) -> set the nominal current of the load: 20A (caution: the nominal current of the load may differ from the
rating of the current sensor (CT1) used: a 63A current sensor can be used to monitor a 20A circuit breaker.
CT1 -> current measured by the current sensor connected to input: I01, I02, I03.
LOAD
|
I-30@4 ID:FOC1D2
LOAD
L1
NAME LOAD 1
TYPE 3P+N_3CT
NOMINAL I (A) 00020
CT1 I01
Go to "CT settings" to perform the conguration of current sensors.
LOAD
|
I-30@4 ID:FOC1D2
NAME LOAD 1
TYPE 3P+N_3CT
NOMINAL I (A) 00020
CT1 I01
CT settings
Congure:
WAY -> Direction of the current sensor +/DIRECT, -/INV.
V Line -> V1, V2, V3 (position of the current sensor on phase 1, phase 2 or phase 3).
CT -> Indicates the rating of the current sensor used. Click on “DETECT” to automatically detect the rating. After2
seconds, the rating is displayed.
Complete the process by selecting "OK" then "OK" again