This allows you to allocate Modbus addresses to the connected devices within a specic range:
AUTODETECT.
|
START ADDRESS 001
END ADDRESS 247
NB ADDR. POSSIBLE 032
ADDR. SET METHOD AUTO SET
APPLY SETTINGS
Choose the conict resolution method (“ADDR. SET METHOD”):
- “PUSH BUTTON”: you must press the push button on each module to resolve address conicts. The order you
will use to press the push buttons on the modules will also determine the order for the Modbus addressing of
those modules.
- “AUTOSET”: connected devices are automatically allocated individual Modbus addresses within the specied
range.
Click on “APPLY SETTINGS” to apply your modications.
Choose the auto-discovery “METHOD”:
AUTODETECT.
|
STATUS STOPPED
FOUND / CONFLICT 000 / 000
DIGIWARE ADDRESSING RANGE 001:247
METHOD
FAST
START
- FAST (default mode): this mode will only detect DIRIS Digiware modules on the Digiware bus and RS485 bus,
DIRIS B and DIRIS A-40 on the RS485 bus.
- FULL: this mode will also detect other Socomec PMDs (DIRIS A) and meters (COUNTIS E) connected on the
RS485 bus.
Click on "START" then "OK" to start the auto-discovery process (this can take up to 5 minutes).
AUTODETECT.
|
STATUS STOPPED
FOUND / CONFLICT 000 / 000
DIGIWARE ADDRESSING RANGE 001:247
METHOD FAST
START