Suppression mode ("Y" option)
This additional function is interesting, for example, in level
measurement with troublesome agitators. The sensor can be
stopped by an external signal. For this purpose, the
Teach/Sync. line is powered externally with a signal of 1...3
VDC. As long as this voltage is present, the sensor no longer
transmits and keeps the last measured distance. To
reactivate the sensor, the external power source has to be
removed (not on mass, but separated at high impedance!).
Cable
The sensors have an M12 4-pin connector for screw
mounting. The potentiometer versions have an integrated
cable. The cable should not be mounted parallel or close to
high current cables. Cables have to be ordered separately.
Setting the switching point on the potentiometer version
This sensor has one switching point. The potentiometer has
3 turns and no stop.
Place the target on the switching point
Turn potentiometer completely counter clockwise
Then turn slowly clockwise until the LED lights
Inclination angle of object
Smooth surfaces can be detected up to an inclination angle
of 10°. However rough and structured (granular) surfaces
can be detected up to much higher angles.
Dimensions
M12x1
M18x1
77
37
63
Teach-in version, axial sensing direction
axiale Messrichtung
M18x1
M12x1
95
81
55
Teach-in version, axial sensing direction
M18x1
36
77
Potentiometer version, axial sensing direction
M18x1
54
94
Potentiometer version, radial sensing direction