User manual
Installation
17
EN
U.S. and Canada installation / 4-wire 
branch circuit
• Separate the green or yellow-green 
wires from the white wires that extend out 
of the end of the appliance cable.
• The ground wire must be connected first.
• Connect the green or yellow-green 
ground wire from the appliance to the 
ground wire in the junction box (green 
colored wire) using UL/CSA listed wire 
connectors. Do not connect the 
grounding wire to the neutral wire in the 
junction box.
• Connect the red and black leads from 
the appliance to the matching color 
wires in the junction box using UL/CSA 
listed wire connectors.
• Connect the white wire from the 
appliance to the neutral white wire in the 
junction box using a UL/CSA listed wire 
connector.
•  Connect to a 20A fuse or circuit breaker. 
Connect to copper wire, or, if 
connection is made to aluminum house 
wiring, use UL-listed or CSA-approved 
connectors approved for joining 
aluminum and copper wiring.
A cable from power supply bw black wires
B junction box gw white-green or yellow-green wires
C cable from range rw red wires
D UL/CSA listed conduit connector ww white wires
NOTE: Both leads coming out of 
the range must be connected 
according to the diagrams shown 
in figures.