Datasheet

How to Order
PF3W 7 04 03 AT M
Type
Remote sensor unit
Integrated display
5
7
Integrated
display
PF3W 5 04 03 1T
Remote
sensor unit
Thread type
N
F
Rc
NPT
G
0.5 to 4
l
/min
2 to 16
l
/min
5 to 40
l
/min
10 to 100
l
/min
04
20
40
11
Rated flow range (Flow range)
Symbol Rated flow range
Bracket (Option)
None
Bracket
R
Made to Order
(Refer to page 6.)
Seal material EPDM
X109
Output specification/
Temperature sensor
Symbol
OUT1
Flow rate
Flow rate Temperature
NPN
PNP
Analogue 1 to 5 V
Analogue 4 to 20 mA
Analogue 1 to 5 V
Analogue 4 to 20 mA
A
B
C
D
E
F
G
H
AT
BT
CT
DT
ET
FT
NPN
PNP
Analogue 1 to 5 V
Analogue 4 to 20 mA
Analogue 1 to 5 V
Analogue 4 to 20 mA
External input
Note 1)
External input
Note 1)
(NPN)
(PNP)
(Analogue 1 to 5 V)
(Analogue 4 to 20 mA)
(Analogue 1 to 5 V)
(Analogue 4 to 20 mA)
NPN
PNP
NPN
NPN
PNP
PNP
NPN
PNP
NPN
PNP
NPN
NPN
PNP
PNP
100
l
/min type is not available with flow
adjustment valve.
None
Yes
S
Flow adjustment valve
Symbol
Rated flow rate
With/without flow
adjustment valve
04
20
40
11
Port size
Symbol
Port
size
Rated flow range
03
04
06
10
04
20
40
11
3/8
1/2
3/4
1
Calibration certificate
(Only flow sensor)
None
With calibration certificate
A
The certificate is written in both English and
Japanese. Integrated display type with
temperature sensor can only display flow rate.
Options/Part No.
When optional parts are required separately, use the following part numbers to place an order.
Part no. Qty.
1
1
1
1
Note
Description
ZS-40-K
ZS-40-L
ZS-40-M
ZS-40-A
For PF3W704/720/504/520
For
PF3W740/540
For
PF3W711/511
Bracket
Note)
Lead wire with M8 connector
Note 1) External input:
The accumulated
value, peak
value, and
bottom value can
be reset.
Note 2) For units with
temperature
sensor, OUT2
can be set as
either tempera-
ture output or
flow rate output.
Setting when
shipped is for
temperature
output.
Note) For units with flow adjustment valve, 2 brackets are required.
With 4 tapping screws (3 x 8)
With 4 tapping screws (3 x 8)
With 4 tapping screws (4 x 10)
Lead wire length (3 m)
Integrated display/Unit specification
Symbol
Temperature
Instantaneous
flow rate
M
G
F
J
Accumulated
flow
°C
°C
°F
°F
l
/min
gal/min
gal/min
l
/min
l
gal
gal
l
Remote sensor unit/
Unit printed on label
Symbol Temperature
Instantaneous
flow rate
G
F
J
Accumulated
flow
°C
°C
°F
°F
l
/min
gal/min
gal/min
l
/min
l
gal
gal
l
Note) G, F, J: Made to Order
Reference: 1 [
l
/min] 0.2642 [gal
/min]
1 [gal
/min
] 3.785 [
l
/min]
°F = 9/5°C + 32
Note) G, F, J: Made to Order
Reference: 1 [
l
/min] 0.2642 [gal
/min]
1 [gal
/min
] 3.785 [
l
/min]
°F = 9/5°C + 32
OUT2
Temperature
sensor
None
With
temperature
sensor
Note 2)
Note 2)
Note 2)
Note 2)
Note 2)
Note 2)
Integrated display
Output specification/Temperature sensor
Symbol
OUT1
Flow rate
OUT2
Temperature
Temperature sensor
1
2
1T
Analogue 1 to 5 V
With temperature sensor
None
Analogue 1 to 5 V
Analogue 4 to 20 mA
Analogue 1 to 5 V
Remote sensor unit
Series
PF3W
3-colour display
Digital Flow Switch for Water
Lead wire
With lead wire with M8
connector
(3 m)
N
Without lead wire
with M8
connector
®
RoHS
Specifications (Integrated Display)
Temperature Sensor Specifications
Note 1) The rated temperature range is for the temperature sensor alone.
The fluid temperature range specification of the flow switch as a whole
is 0 to 90°C.
Note 2) The response time is for the temperature sensor alone.
The OUT2 can be selected from the output for temperature or flow
rate by button operation.
Note 1) Refer to “Measurable Range for Ethylene Glycol Aqueous Solution” on page 4. Measurement can be performed with a fluid that does not corrode wetted parts
and has viscosity of 3 mPa·s [3 cP] or less.
Note 2) When 0.5 s is selected for the response time of the switch output, the repeatability becomes ±3% F.S.
Note 3) Operating pressure range and proof pressure change according to the fluid temperature. Refer to page 3.
Note 4) Cleared by turning off the power supply. It is possible to select the function to memorise it. (Every 2 or 5 minutes) When 5 minutes memorising is selected, the
lifetime of the memory element (electronic part) is 1 million times (5 minutes x 1 million times = 5 million minutes = Approx. 9.5 years for 24 hour energizing).
Calculate the lifetime based on your operating conditions before using the memorising function, and do not exceed it.
Note 5) The response time when the set value is 90% in relation to the step input. (The response time is 7 s when it is output by the temperature sensor.)
Note 6)
The response time until the set value reaches 90% in relation to the step input. (The response time is 7 s when it is analogue output by the temperature sensor.)
Note 7) When the temperature sensor is used, it will be 250 VAC.
Note 8) Refer to “Wetted Parts Construction” on page 7 for details.
Model
PF3W704 PF3W720 PF3W711PF3W740
Applicable fluid
Detection method
Rated flow range
Display flow range
Set flow range
Minimum setting unit
Conversion of accumulated pulse (Pulse width: 50 ms)
Fluid temperature
Display unit
Accuracy
Repeatability
Temperature characteristics
Operating pressure range
Note 3)
Proof pressure
Note 3)
Pressure loss
Accumulated flow range
Note 4)
Switch output
Hysteresis
External input
Display method
Indicator light
Power supply voltage
Current consumption
Environment
Standards and regulations
Wetted parts material
Note 8)
Piping port size
Maximum load current
Maximum applied voltage
Internal voltage drop
Response time
Note 2), 5)
Output protection
Output
mode
Response time
Note 6)
Voltage output
Current output
Enclosure
Operating temperature range
Operating humidity range
Withstand voltage
Note 7)
Insulation resistance
Without temperature sensor/Without flow adjustment valve
With temperature sensor/Without flow adjustment valve
Without temperature sensor/With flow adjustment valve
With temperature sensor/With flow adjustment valve
With lead wire with connector
Water and ethylene glycol aqueous solution (with viscosity of 3 mPa·s [3 cP] or less)
Note 1)
Karman vortex
0.1
l/min
0 to 90°C (with no freezing and condensation)
Instantaneous flow rate:
l/min, Accumulated flow: l
Display value: ±3% F.S. Analogue output: ±3% F.S.
±2% F.S.
Note 2)
±5% F.S. (25°C reference)
0 to 1 MPa
1.5 MPa
45 kPa at the maximum flow (without flow adjustment valve)
NPN or PNP open collector output
80 mA
28 VDC
NPN: 1 V or less (at 80 mA load current) PNP: 1.5 V or less (at 80 mA load current)
0.5s / 1s / 2s
Short circuit protection
Select from hysteresis mode, window comparator mode, accumulated output mode, or accumulated pulse output mode.
Select from hysteresis mode or window comparator mode.
0.5s / 1s / 2s (linked with the switch output)
Voltage output: 1 to 5 V Output impedance: 1 kΩ
Output current: 4 to 20 mA Max. load impedance: 300 Ω for 12 VDC, 600 Ω for 24 VDC
Variable
Voltage free input: 0.4 V or less (Reed or Solid state), input for 30 ms or longer
2-screen display (Main screen: 4-digit, 7-segment, 2-colour, Red/Green Sub screen: 6-digit, 11-segment, White) Display values updated 5 times per second
Output 1, Output 2: Orange
12 to 24 VDC ±10%
50 mA or less
IP65
0 to 50°C (with no freezing and condensation)
Operation, Storage: 35 to 85% R.H. (with no condensation)
1000 VAC for 1 minute between whole live part and enclosure
50 MΩ or more (500 VDC mega metre) between whole live part and enclosure
CE marking, UL (CSA), RoHS
PPS, Stainless steel 304, FKM, SCS13
Non-grease
2 to 16
l/min
1.7 to 22.0
l/min
0.1
l
/pulse
5 to 40
l/min
3.5 to 55.0
l/min
0.5
l
/pulse
10 to 100
l/min
7 to 140
l/min
1
l/min
1
l
/pulse
0.5 to 4
l/min
0.35 to 5.50
l/min
0.01
l/min
0.05
l
/pulse
3/8, 1/2
260 g
335 g
360 g
435 g
1/2, 3/4
410 g
530 g
610 g
730 g
3/4, 1
720 g
860 g
3/8
210 g
285 g
310 g
385 g
By 0.1
l By 0.5 l
99999999.9 l
999999999 l
By 1 l
The output related to the temperature sensor is OUT2 only.
Flow rate detecting circuit
OUT1 Switch output
OUT2 Switch output
Analogue output
Main circuit
Temperature detecting circuit
Brown DC (+)
Black OUT1
White OUT2
Blue DC (–)
Flow rate
Temperature
+85 g
0.35 to 5.50
l/min
(Flow under 0.35 l/min is displayed as “0.00”)
1.7 to 22.0 l/min
(Flow under 1.7 l/min is displayed as “0.0”)
3.5 to 55.0 l/min
(Flow under 3.5 l/min is displayed as “0.0”)
7 to 140 l/min
(Flow under 7 l/min is displayed as “0”)
Weight
Analogue output
Rated temperature range
Setting/Display temperature range
Minimum setting unit
Display unit
Display accuracy
Analogue output accuracy
Response time
Ambient temperature characteristics
0 to 100°C
Note 1)
–10 to 110°C
1°C
°C
±2°C
±3% F.S.
7 s
Note 2)
±5% F.S.
3-Colour Display Digital Flow Switch for PVC Piping
PF3W
3-Colour Display Digital Flow Monitor for Water
PF3W3
3-Colour Display Digital Flow Switch for Water
PF3W
Function
Details
Digital Flow Switch for Water
Series
PF3W
3-colour display
2