Datasheet

Output
Fluid
temperature
C
D
B
A
100°C0°C–10°C 110°C
0
Output
Minimum
rated flow
Maximum
rated flow
Flow rate
A
C
B
Specifications
Note 1) Cleared by turning off the power supply. It is possible to select the function to memorise it. (Every 2 or 5 minutes) When 5 minutes memorising is selected, the
lifetime of the memory element (electronic part) is 1 million times (5 minutes x 1 million times = 5 million minutes = Approx. 9.5 years for 24 hour energizing).
Calculate the lifetime based on your operating conditions before using the memorising function, and do not exceed it.
Note 2) The response time when the set value is 90% in relation to the step input. (The response time is 7 s when it is output by the temperature sensor.)
Note 3)
The response time until the set value reaches 90% in relation to the step input. (The response time is 7 s when it is analogue output by the temperature sensor.)
Model
PF3W30
Display flow range
Set flow range
Minimum setting unit
Conversion of accumulated pulse
Display unit
Accuracy
Repeatability
Temperature characteristics
Accumulated flow range
Note 1)
Switch output
Hysteresis
External input
Input/output
Display method
Indicator light
Power supply voltage
Current consumption
Connection
Environment
Standards and regulations
Weight
Analogue output
Maximum load current
Maximum applied voltage
Internal voltage drop
Response time
Note 2)
Output protection
Output
mode
Response time
Note 3)
Voltage output
Current output
Enclosure
Operating temperature range
Operating humidity range
Withstand voltage
Insulation resistance
Without power supply/output connection lead wire
With power supply/output connection lead wire
1
l
/min
1
l
/pulse
0.1
l
/min
Instantaneous flow rate:
l
/min, Accumulated flow:
l
Display value: ±0.5% F.S. Analogue output: ±0.5% F.S.
±0.5% F.S.
±0.5% F.S. (25C reference)
NPN or PNP open collector output
80 mA
28 VDC
NPN: 1 V or less (at 80 mA load current) PNP: 1.5 V or less (at 80 mA load current)
1s / 2s
Short circuit protection
Select from hysteresis mode, window comparator mode, accumulated output mode, or accumulated pulse output mode.
Select from hysteresis mode or window comparator mode.
1s / 2s (linked with the switch output)
Voltage output: 1 to 5 V Output impedance: 1 kΩ
Output current: 4 to 20 mA Max. load impedance: 300 Ω for 12 VDC, 600 Ω for 24 VDC
Variable
Voltage free input: 0.4 V or less (Reed or Solid state), input for 30 ms or longer
Input for copy mode
2-screen display (Main screen: 4-digit, 7-segment, 2-colour, Red/Green Sub screen: 6-digit, 11-segment, White), Display values updated 5 times per second
Output 1, Output 2: Orange
12 to 24 VDC ±10%
50 mA or less
Power supply output 5P connector, sensor connection 4P connector (e-con)
IP40 (Only front face of the panel is IP65 when panel mount adapter and waterproof seal of optional parts are used.)
0 to 50°C (with no freezing and condensation)
Operation, Storage: 35 to 85% R.H. (with no condensation)
1000 VAC for 1 minute between whole live part and enclosure
50 M or more (500 VDC mega metre) between whole live part and enclosure
CE marking, UL (CSA), RoHS
50 g
100 g
1.7 to 18.0
l
/min
0.1
l
/pulse
3.5 to 45.0
l
/min
0.5
l
/pulse
7 to 112
l
/min
0.35 to 4.50
l
/min
0.01
l
/min
0.05
l
/pulse
By 0.5
l
By 0.1
l
99999999.9
l
999999999
l
By 1
l
Flow rate
Temperature
Temperature Sensor Specifications
Note 1) The rated temperature range is for the temperature sensor alone.
The fluid temperature range specification of the flow switch as a whole
is 0 to 90°C.
Note 2) The response time is for the temperature sensor alone.
The OUT2 can be selected from the output for temperature or flow
rate by button operation.
Rated temperature range
Setting/Display temperature range
Minimum setting unit
Display unit
Analogue output accuracy
Response time
Ambient temperature characteristics
0 to 100°C
Note 1)
–10 to 110°C
1°C
°C
±3% F.S.
7 s
Note 2)
±5% F.S.
The output related to the temperature sensor is OUT2 only.
Analogue Output
Flow rate/Analogue output Fluid temperature/Analogue output
Voltage output
Current output
0.6 V
2.4 mA
A
1 V
4 mA
B
Voltage output
Current output
1 V
4 mA
A
1.5 V (1.4 V)
6 mA (5.6 mA)
B
5 V
20 mA
C
PF3W504
PF3W520
PF3W540
PF3W511
0.5
2
5
10
Minimum
Model
Rated flow [
l
/min]
4
16
40
100
Maximum
Voltage output
Current output
5 V
20 mA
C
5.4 V
21.6 mA
D
OUT1 Switch output
Analogue output
OUT2 Switch output
Analogue output
Remote monitor unit
Brown DC (+)
Black OUT1
White OUT2
Blue DC (–)
DC (+) Brown
Flow rate
1 to 5 V Black
Temperature
1 to 5 V White
DC (–) Blue
Remote
sensor
unit
Values in parentheses are for the
combination with the PF3W511.
Be sure to use in combina-
tion with remote sensor units
with temperature sensor.
0.35 to 4.50
l
/min
(Flow under 0.35 l/min is displayed as “0.00”)
1.7 to 18.0
l
/min
(Flow under 1.7
l
/min is displayed as “0.0”)
3.5 to 45.0
l
/min
(Flow under 3.5
l
/min is displayed as “0.0”)
7 to 112
l
/min
(Flow under 7
l
/min is displayed as “0”)
Main circuit
Series PF3W3
12 to 24 VDC
Brown DC (+)
Black OUT1
White
Analogue output
Grey COPY
Blue DC (–)
Load
Load
Brown DC (+)
Black OUT1
White
External input
Grey COPY
Blue DC (–)
12 to 24 VDC
Load
Brown DC (+)
Black OUT1
White OUT2
Blue DC (–)
12 to 24 VDC
Load
Load
Grey COPY
12 to 24 VDC
Brown DC (+)
Black OUT1
White OUT2
Grey COPY
Blue DC (–)
Load
Load
Brown DC (+)
Black OUT1
Blue DC (–)
12 to 24 VDC
White
Analogue output
Grey COPY
Load
Load
Brown DC (+)
Black OUT1
White
External input
Grey COPY
Blue DC (–)
12 to 24 VDC
Load
12 to 24 VDC
Brown DC (+)
Black
Analogue output
White
Analogue output
Grey COPY
Blue DC (–)
Load
Load
r
e
w
q
Black
Blue
White
Brown
1 to 5 V (Flow rate)
DC (–)
N.C./1 to 5 V (Temperature)
DC (+)
Main circuitMain circuitMain circuit
Main circuitMain circuitMain circuit
Main circuit
Main circuit
Example of Internal Circuit and Wiring
NPN 2 Output type
PF3W30A
NPN + Analogue output type
PF3W30C
NPN + Analogue output type
PF3W30D
NPN + External input type
PF3W30G
PNP + External input type
PF3W30H
PNP + Analogue output type
PF3W30E
PNP + Analogue output type
PF3W30F
PNP 2 Output type
PF3W30B
Analogue 2 Output type
PF3W30J/PF3W30K
Sensor input circuit
3-Colour Display Digital Flow Monitor for Water
PF3W3
3-Colour Display Digital Flow Switch for PVC Piping
PF3W
3-Colour Display Digital Flow Switch for Water
PF3W
Function
Details
3-colour display
Digital Flow Monitor for Water
Series
PF3W3
18