Displays the set value. (The set value 
of OUT2 cannot be displayed.)
Displays the accumulated value. (The 
accumulated value of OUT2 cannot be 
displayed.)
Displays the peak value.
Displays the line name. (Up to 6 
alphanumeric characters can be input.)
Displays the fluid temperature.
(When the temperature sensor type is
selected.)
Displays nothing.
Displays the bottom value.
Series PF3W
Function Details 1
Set value display Accumulated value display Peak value display Bottom value display
! Selection of display on sub screen
The display on the sub screen in measuring mode can be set.
! Output operation
The output operation can be selected from the following:
Output (hysteresis mode and window comparator mode) corresponding 
to instantaneous flow rate,
Output corresponding to accumulated flow,
Accumulated pulse output
Note) At the time of shipment from the factory, it is set to hysteresis 
mode and normal output.
When a temperature sensor is attached, the output to the temperature 
sensor is selectable only for OUT2.
(Refer to “How to Order” for details.)
ON: Green, OFF: Red
ON: Red, OFF: Green
Always: Red
Always: Green
! Indication color
The  indication  color  can  be  selected  for  each 
output condition. The selection of the indication 
color  provides  visual  identification  of  abnormal 
values. (The indication color depends on OUT1 
setting.)
0.5 seconds
1 second
2 seconds
$
$
$
—
$
$
! Response time
The response time can be selected depending on the application. (1 
second for default setting)
Abnormalities can be  detected more quickly by  setting the response 
time to 0.5 seconds.
The effect of the pump fluctuation and flickering of the display can be 
reduced by setting the response time to 2 seconds.
Note) The temperature sensor output is fixed to 7 seconds.
Response
time
Applicable model
Integrated display
Series PF3W7
Remote monitor unit
Series PF3W3
! External input function
This function can be used when external input is available. The accumulated 
value, peak value, and bottom value can be reset by remote control.
Accumulated flow external reset:
This function resets the accumulated value to “0” when an input signal 
is applied.
In  accumulated  increment  mode,  the  value  will  be  zero  when  reset, 
and the accumulated value will increase from zero.
In accumulated decrement mode, the value will be the set value when 
reset, and the accumulated value will decrease from the set value.
  When  the  accumulated  value  is  memorized,  every  time  the  accumulated 
value  external  reset  is  activated,  the  memory  element  (EEPROM)  will  be 
accessed.  Take  into  consideration  the  maximum  number  of  times  the 
memory  element  can  be  accessed,  1  million  times.  The  total  of  external 
input  times  and  accumulated  value  memorizing  time  interval  should  not 
exceed 1 million times.
Peak and bottom reset: Peak and bottom values are reset.
! Forced output function
Output  is  turned  ON/OFF  compulsorily  when  starting  the  system  or 
during  maintenance.  This  enables  confirmation  of  the  wiring  and 
prevents system errors due to unexpected output.
For the analog output type, the output will be 5 V or 20 mA for ON and 
1 V or 4 mA for OFF.
 Also, the increase or decrease of the flow and temperature will not 
change  the  on/off  status  of  the  output  while  the  forced  output 
function is activated.
! Accumulated value hold function
Accumulated  value  can  be  saved  on  the  unit  even when  the power 
supply is turned off.
The  accumulated  value  is  memorized  every  2  or  5  minutes  during 
measurement,  and  continues  from  the  last  memorized  value  when 
the power supply is turned on again. 
The lifetime of the memory element is 1 million access cycles. Take 
this into consideration before using this function.
! Peak/Bottom value indication
The  maximum  (minimum)  flow  is  detected  and  updated  from  when 
the  power  supply  is  turned  on.  In  peak  (bottom)  value  indication 
mode, this maximum (minimum) flow is displayed.
! Setting of secret code
Users can  select whether a  secret code  must be  entered to  release 
key lock. At the time of shipment from the factory, it is set such that 
the secret code is not required.
! Power saving mode
The display can be turned off to reduce the power consumption.
In power saving mode, decimal points blink on the main screen.
If  any  button  is  pressed  during  power  saving  mode,  the  display  is 
recovered for 30 seconds to check the flow, etc.
! Keylock function
Prevents  operation  errors  such  as  accidentally  changing  setting 
values.