Datasheet

How to Order
Series PF2A
Digital Flow Switch/High Flow Rate Type
High flow rate type
03
06
12
Flow rate range
150 to 3000 l/min
300 to 6000
l/min
600 to 12000
l/min
Symbol
10
14
20
Port size
1
1
1
/
2
2
3000
6000
12000
Port
size
Applicable
model
Flow rate (
l/min)
28
29
68
69
Output specification
NPN open collector 1 output + Analog output (1 to 5 V)
NPN open collector 1 output + Analog output (4 to 20 mA)
PNP open collector 1 output + Analog output (1 to 5 V)
PNP open collector 1 output + Analog output (4 to 20 mA)
Nil
N
F
Port specification
Rc
NPT
G
PF2A703H
PF2A706H
PF2A712H
For Air
Specifications
H
Nil
M
With unit switching function
Fixed SI unit
Note)
Note) Fixed units:
Real-time flow rate:
l/min
Accumulated flow:
l, m
3
, m
3
x 10
3
Unit specification
Switching of switch output and accumulated pulse output is possible with
NPN or PNP open collector outputs.
PF2A7
Nil
N
Lead wire (Refer to page 35.)
M12
3 m lead wire with connector
Without lead wire
M
11
Refer to www.smcworld.com for details of
products compatible with overseas standards.
Integrated
Display Type
Model
Measured fluid
Detection type
Rated flow range
Note 1)
Minimum set unit
Note 1)
Operating pressure range
Proof pressure
Pressure loss
Accumulated flow range
Linearity
Note 3)
Repeatability
Pressure characteristics
Temperature characteristics
Output
specifications
Response time
Hysteresis
Power supply voltage
Current consumption
Weight
Port size (Rc, NPT, G)
Note 2)
Display units
Real-time flow rate
Accumulated flow
Resistance
Enclosure
Operating temperature range
Withstand voltage
Insulation resistance
Vibration resistance
Impact resistance
Noise resistance
PF2A703H
150 to 3000 l/min
5
l/min
PF2A706H
Dry air, Nitrogen
Heater type
300 to 6000
l/min
l/min, CFM
l, m
3
, m
3
x 10
3
, ft
3
, ft
3
x 10
3
, ft
3
x 10
6
0.1 to 1.5 MPa
2.25 MPa
20 kPa (at maximum flow rate)
0 to 9,999,999,999
l
±1.5% F.S. or less (0.7 MPa, at 20°C)
±1.0% F.S. or less (0.7 MPa, at 20°C), ±3.0% of F.S. or less in case of analog output
±1.5% F.S. or less (0.1 to 1.5 MPa, based on 0.7 MPa)
±2.0% F.S. or less (0 to 50°C, based on 25°C)
1 sec. or less
Hysteresis mode: Variable (can be set from 0); Window comparator mode: (can be set from 0 to 3% F.S.)
24 VDC (ripple ±10% or less)
150 mA or less
IP65
0 to 50°C (with no freezing and condensation)
1000 VAC for 1 min. between external terminal and case
50M (500 VDC Mega) between external terminal and case
10 to 500 Hz with a 1.5 mm amplitude or 98 m/s
2
acceleration, in each X, Y, Z direction for 2 hrs, whichever is smaller.
490 m/s
2
in X, Y, Z directions 3 times each
1000 Vp-p, Pulse width 1 µs, Rise time 1 ns
1.3 kg (without lead wire)
1
1
/
2
PF2A712H
600 to 12000 l/min
10
l/min
NPN open collector Max. load current: 80 mA; Max. applied voltage: 30 V; Internal voltage drop: 1 V or less (with load current of 80 mA)
PNP open collector Max. load current: 80 mA; Internal voltage drop: 1.5 V or less (with load current of 80 mA)
Switch output
Note 4)
Analog output
Note 5)
Accumulated
Note 4)
pulse output
Note 1) Flow rate display can be switched between the basic condition of 0°C, 101.3 kPa and the standard condition (ANR) of 20°C, 101.3 kPa, and 65% RH.
Note 2) For digital flow switch with unit switching function. (Fixed SI unit [(
l/min, or l, m
3
or m
3
x 10
3
)] will be set for switch type without the unit switching function.)
Note 3) The high flow rate type is CE marked; however, the linearity with applied noise is ±5% F.S. or less.
Note 4) Switch output and accumulated pulse output selections are made using the button controls.
Note 5) The analog output operates only for real-time flow rate, and does not operate for accumulated flow.
2.0 kg (without lead wire)
2
1.1 kg (without lead wire)
1
Output voltage: 1 to 5 V; Load impedance: 100 k or more
Output current: 4 to 20 mA; Load impedance: 250 or less
NPN or PNP open collector
Flow rate per pulse: 100
l/pulse, 10.0 ft
3
/pulse
ON time per pulse width: 50 msec