Datasheet
5
Brown DC (+)
Black OUT1
White OUT2
Blue DC (−)
24 VDC
Load
Load
24 VDC
Brown DC (+)
Black OUT1
White OUT2
Blue DC (−)
Load
Load
Brown DC (+)
Black OUT1
Blue DC (−)
24 VDC
White Analogue output
Load
Load
Main circuit
Main circuit
Main circuit
Max. 80 mA
Brown DC (+)
Black OUT1
White OUT2
Load
Load
50 ms
0 V
50 ms
or
50 ms
0 V
50 ms
or
Accumulated pulse output wiring examples
Black OUT1
White OUT2 (LFE쏔A쏔쏔쏔 only)
Blue DC (−)
Load
Load
Max. 28 V, 80 mA
Internal Circuits and Wiring Examples (Integrated Display Type)
NPN 2 outputs type
LFE쏔A쏔쏔쏔
NPN + Analogue output type
LFE쏔C쏔쏔쏔
NPN + Analogue output type
LFE쏔D쏔쏔쏔
NPN 2 outputs type
LFE쏔A쏔쏔쏔
NPN + Analogue output type
LFE쏔C쏔쏔쏔/LFE쏔D쏔쏔쏔
PNP 2 outputs type
LFE쏔B쏔쏔쏔
PNP 2 outputs type
LFE쏔B쏔쏔쏔
Max. 28 V, 80 mA
Internal voltage drop 1 V or less
Max. 80 mA
Internal voltage drop 1.5 V or less
Max. 28 V, 80 mA
Internal voltage drop 1 V or less
C: Analogue output 1 to 5 V
Output impedance 1 kΩ
D: Analogue output 4 to 20 mA
Load impedance 50 to 600 Ω
∗ When accumulated pulse output is selected, the indicator light is turned off.
Brown DC (+)
N.C.
Blue DC (−)
24 VDC
White Analogue output
Load
Internal Circuits and Wiring Examples (Remote Type Sensor Unit)
Analogue output type
LFE쏔J쏔쏔쏔 (Voltage output type)
LFE쏔K쏔쏔쏔 (Current output type)
Main circuit
∗ Do not connect N.C.
Series LFE