Brochure
Specific Product Precautions 5
Regulating pressure range, by unit of standard measured pressure
Unit
MPa
kgf/cm
2
bar
psi
kPa
Set Pressure Range
CE Mark
The regulating pressure range, by unit of standard
measured pressure, is shown in the table below.
In case that a CE marked ITV (including a special
product) is used with a cable which is purchased
separately, mount a ferrite core to the cable if it is
necessary according to the table below.
ITV
01
ITV
03
Regulating pressure range
ITV
05
0.005 to 0.1
0.05 to 1
0.05 to 1
0.7 to 15
5 to 100
0.005 to 0.5
0.05 to 5
0.05 to 5
0.7 to 70
5 to 500
Model Ferrite core
Recommended
power cable part No.
ITV0000--Q
ITV0000 series
Not necessary M8-4DSX3MG4
(Straight type)
ELWIKA-KV4408 PVC025 2M
(Right angle type)
Model Ferrite core
Recommended
power cable part No.
ITV--Q
ITV1000/2000/3000 series
Necessary
ITV-CC-Q
Not necessary
ITV-DN-Q
Necessary
(Ferrite core is
attached to the body)
ITV-PR-Q
ITV-RC-Q
Necessary
(Ferrite core is
attached to the body)
P398010-12 (Straight type)
(With ferrite core)
P398010-13 (Right angle
type) (With ferrite core)
P398020-500-3
(Straight type)
P398020-501-3
(Right angle type)
P398020-504-3
(Straight type)
P398020-505-3
(Right angle type)
P398020-500-3
(Straight type)
P398020-501-3
(Right angle type)
0.005 to 0.9
0.05 to 9
0.05 to 9
0.7 to 130
5 to 900
Series ITV0000/1000/2000/3000
ITV209
—
—
—
—
–1.3 to –80
Note) Length of the recommended cable is 3m (however, ELWIKA-
KV4408 PVC025 2M is 2 metres. Consult SMC for length of other cables)
Series ITV1000/2000/3000/209 Precautions
Be sure to read before handling. Refer to back pages 1 and 2 for Safety Instructions,
“Handling Precautions for SMC Products” (M-E03-3) for Common Precautions.
Specific Product Precautions 6
Series ITV0000/1000/2000/3000
Handling
1. Connect the vacuum pump to the port, which is la-
beled “VAC”.
2.
Pressure adjustment changes from “atmospheric
pressure to vacuum pressure” when the input sig-
nal is increased, and from “vacuum pressure to at-
mospheric pressure” when the input signal is de-
creased.
3.
When adjusting the vacuum pressure, be careful not
to block the atmospheric pressure inlet port labeled
“ATM”.
4.
Since this product is designed exclusively for use
with negative pressure, be careful not to apply posi-
tive pressure in error.
5. In cases where the vacuum pump being used has a
relatively small capacity, or the piping has a small
inside diameter, etc., large variations in the set
pressure (the range of pressure variation when
changing from no flow to flow state) may appear. In
this situation, the vacuum pump or the piping, etc.
should be changed. In cases where it is not practi-
cal to change the vacuum pump, install a capacity
tank (volume depending on the operating condi-
tions) on the VAC side.
6. The vacuum pressure response time after a change
in the input signal is influenced by the internal volu-
me on the setting side (including piping). Since the
capacity of the vacuum pump also influences the
response time, give careful consideration to these
points before operation.
7.
If the electric power is shut off when in a control
state, the pressure on the setting side will go into a
holding condition. However, this setting side pres-
sure will be held only temporarily and is not guaran-
teed. In addition, when atmospheric pressure is de-
sired, shut off the power after reducing the set pres-
sure, and then introduce atmospheric pressure by
using a vacuum release valve, etc.
8.
If the power for this product is cut off by a power
failure, etc. when it is in a controlled state, the set-
ting side pressure will be held temporarily. Further,
if operated without sealing the setting side so that
atmospheric air is sucked in, handle with care as air
will continue to be sucked in.
9.
If the VAC side pressure to this product is interrup-
ted while the power is still on, the internal solenoid
valve
will continue to operate and may cause a
humming noise. Since this may shorten the life of
the product, be sure to shut off the power when the
VAC side pressure is shut off.
10.
The setting side pressure cannot be completely re-
leased from this product in the range below –1.3
kPa. In cases where the pressure needs to be redu-
ced completely to 0 kPa, install a 3 port valve, etc.
on the setting side to discharge the residual pressu-
re.
11.
This product is adjusted for each specification at the
factory before shipment. Avoid careless disas
-
sembly or removal of parts, as this can cause failu
-
re.
12. The optional cable connector is a 4-wire type. When
the monitor output (analog output, switch output) is
not being used, keep
it from touching the other wi-
res, as this can cause malfunction.
13.
Use caution that the right angle cable does not rota-
te and is limited to only one entry direction.
14.
Take the following steps to avoid malfunction due to
noise.
1) Eliminate power supply noise during operation by installing
a line filter, etc. in the AC power line.
2) For avoiding the influence of noise or static electricity, install
this product and its wiring as far as possible from strong
electric fields such as those of motors and power lines, etc.
3) Make sure to take protective measures against load surge
for an induction load (solenoid valves, relays, etc.).
15.
Refer to the instruction manual included with the
product for details on its handling.
Caution
Series ITV009/209 Precautions
Be sure to read before handling. Refer to back pages 1 and 2 for Safety Instructions,
“Handling Precautions for SMC Products” (M-E03-3) for Common Precautions.