Operation Manual
2 Transportation / Installation 
2 - 5 
2-3  Cautions about Reinstallation 
Caution 
No one but someone who has enough knowledge about the product and 
incidental devices should reinstall in another place. And following instructions 
must be executed. 
If you move the product and reinstall it into another place after some operations (including trial running), 
instructions that are not only following ones but also all of those in the chapter 2 should be followed. 
Disassembly of the power cable 
Cut off the power source when you disassemble the power cable. 
Disassembly of the air piping 
•  Remove the seal tape completely after detaching the piping. Remained tape will cause imperfect cooling 
and failure by entering into the body of the product. 
Residual compressed air pressure release procedure 
•  Even while the dryer is removed, only when compressed air is needed, open the bypass piping valve. 
•  Close the compressed air inlet and outlet valve. 
•  Unscrew the front panel fixing screw (in 2 points) and remove the front panel with upholding it a little. 
•  Open the residual pressure release cock of auto drain tube, and release compressed air pressure left inside of 
the product. Refer to the figure at right. 
Warning 
No one but qualified personnel should do the electric wiring. 
Cut off the power supply for safety before the wiring. Do not work under energized 
condition. 
Warning 
No one but qualified personnel should do the air piping. 
Separate the compressor from the product for safety before removing the piping. 
Do not remove any piping when there is remaining compressed air pressure inside 
of it. 
Case Assembly
The ramainder depressure cock.
※It opens when turning in the
 drection og the arrow of figure.