Instruction Manual
HRL-PF002
Particle Filter Set
Thermo-chiller
Applicable model: HRLE090 Series
Read before using
Thank you for purchasing SMC’s Thermo-chiller.
This particle filter set is a set of parts for installing a particle
filter into the piping used in the thermo-chiller HRLE series.
Read and understand the instructions shown below before use.
Safety Instructions
- Safety first, only trained personnel who has knowledge of
general machinery and equipment can perform the installation of
this product.
- Ensure this manual and the Operation Manuals for
thermo-chiller are fully understood.
- Disconnect power from the chiller before performing product
installation. Be sure to check that the power supply is shut off.
- Remove all circulating fluid before performing product
installation.
- Confirm that there is no fluid leakage or condensation after
installation.
1. Parts and Accessories
- This particle filter set includes the following parts.
Please confirm that all of them are present before installation.
Parts
[Materials of wetted parts]
Stainless Steel, Polycarbonate, PTFE, PP, NBR
2. Mounting
1) Select the adapter fitting(Part No.3 or 4) based on the piping to
be installed by the customer.
2) Confirm that no foreign matter such as dust or dirt is adhered to
the connecting ports or the piping where this filter will be fitted.
3) Apply the sealant tape (5) to the fittings, and mount them onto
the inlet of the resin filter case (1).
Caution
・It must not be screwed in too much as it can lead to breakage of the
filter’s ports and/or leakage.
4) Insert the element (2) into the resin filter case (1). Mount the
resin filter case by hand tighten.
Caution
・Mounting of the case should be hand-tightened. When the case is
tightened excessively by tools or handle, the case might crack or be
damaged.
・Make sure that the case is held by hand and removed manually when
mounting the case. If the case is dropped, it may result in cracking or
breakage.
5) Insert the element (2) into the case.
As shown in the figure, insert the element into the case so that
the element fits into the protrusion of the case. Make sure that
the gasket is mounted onto the case correctly. Please note that
the gasket can be removed easily. Keep the element vertical in
the case, and tighten the case into the cap with the handle
(ordered separately). Make sure that the element fits into the
protrusion of the cap.
6) After connecting the piping from the filter to the user's site,
operate the thermo-chiller to check that liquid does not leak.
Please adjust the flow rate so that the initial pressure drop is
0.05MPa or lower. (Approx.100L/min)
7) If air remains in the case, press air release button to discharge
the air as necessary.
* When using the filter, the supply pressure should be 0.5MPa
(72.5psi) or lower.
* Please replace the element when the pressure drop of this product
reaches 0.15MPa. For replacement of the element, confirm the
pressure inside the filter is zero, and refer to mounting procedure
3) and 4).
* Please order HRR-S0079 separately for the special tool that
removes the case.
No.HRX-OM-Z039-A
*The element should be
replaced when the pressure
drop reaches 0.15 MPa.
4. Hex nipple x2pc.
1. Resin filter case
2. Element
(Part No:EJ202S-055X11)
3. RxRc adapter x2pc.
5. Sealant tape
6. Operation manual
(This manual)
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021 JAPAN
Tel: + 81 3 5207 8249 Fax: +81 3 5298 5362
URL
https://www.smcworld.com
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2022 SMC Corporation All Rights Reserved
Revision
Rev. A:July 2022
Cross section of the mounting
Gasket
Element
Case
Protrusion
Protrusion
Cap