User's Manual

SMCSM01-Z Smoke Sensor Quick Start Guide
Copyright
©
2010 SMC Networks
Page 4
All Rights Reserved
I/M SMCSM01-Z rev. 1.0
8/19/10
G.
Line up the new smoke chamber with the optical base by
aligning the arrows on the smoke chamber to the latches
on the optical base and snap down into place.
H.
Replace the detector cap by lining up the cap with the
SMCSM01-Z. Then insert the cap into the SMCSM01-Z and
turn clockwise approximately 15 degrees. The cap snaps
firmly into place when secure.
I.
Insert the batteries into the SMCSM01-Z using the proper
polarity, and replace the battery compartment cover.
J.
Reattach the SMCSM01-Z to its mounting base (see
“Mounting Base Instructions” on this page.
K.
Test the SMCSM01-Z sensitivity and contact the Central
Monitoring Station to place the system back online
(remove from Test mode).
Note: Verify all auxiliary functions for a complete test of
the system.
Maintaining the SMCSM01-Z
The SMCSM01-Z requires minimal maintenance for easy field
service and maintenance.
A.
Test the SMCSM01-Z weekly (see “Sensitivity Testing on
page 3). If it requires maintenance, the LED goes OFF
and a signal is sent to the control panel as described in
the following table.
Note: The SMCSM01-Z does not provide warnings for fires
resulting from explosions, smoking in bed, or other
furniture, ignition of flammable liquids, vapors and gases,
children playing with matches or lighters.
Replacing Batteries
Use only 3V lithium 123 batteries, as listed on the battery
compartment cover.
A.
Remove the SMCSM01-Z from the mounting base (see
“Mounting Base Instructions” on this page).
B.
Slide the battery compartment cover away from the
SMCSM01-Z to unsnap it and lift it off (see the figure on
page 2).
C.
Remove and dispose of the batteries appropriately.
D.
Observe correct polarity and insert two new 3V lithium
batteries into the battery compartment and replace the
cover.
Note: Use only new batteries when replacing old batteries.
Do not replace with batteries that were used previously.
E.
Reattach the SMCSM01-Z to the mounting base and test
the system.
Mounting Base Instructions
To remove the SMCSM01-Z from the mounting base:
A.
Hold the SMCSM01-Z.
B.
Turn it counterclockwise approximately 15 degrees. The
SMCSM01-Z snaps off from the mounting base.
To attach the SMCSM01-Z to the mounting base:
A.
Line up the raised alignment tab on the lip of the
SMCSM01-Z with the arrow on the mounting base (see
the figure on page 2).
B.
Insert the SMCSM01-Z into the base and turn clockwise
approximately 15 degrees. It snaps firmly into place
when secure.
Compliances
The information in this guide is in accordance with NFPA 72 and/or CAN/ULC-
S524, depending on country of installation.
FCC Notice
This device has been designed, constructed, and tested with for compliance with FCC
Rules that regulate intentional and unintentional radiators. As the user of this device,
you are not permitted to make any alterations or modifications to this equipment or to
use it in any way that is inconsistent with the information described in this quick-start
guide, without the express written permission of SMC Networks. Doing so will void
your warranty to operate this equipment. This device complies with Part 15 of the
FCC rules. Operation of this device is subject to the following two conditions:
1) This device may not cause harmful interference, and
2) This device must accept any interference received, including
interference that may cause undesired operation.
The SMCSM01-Z contains FCCID:JI5-SMCZB01 and ICID:4137A-SMCZB01. The
“IC” designation preceding the radio certification number indicates that this
device complies with the Industry of Canada specifications.
ETL Notice: This device complies with all ETL and ETLC safety
requirements.
UL and ULC Notices: This device complies with UL Standard UL268 and ULC
Standard ULC S529.
Smoke detectors are not to be used with detector guards, unless the
combination has been evaluated and found suitable for that purpose.
Signal Meaning
CleanMe SMCSM01-Z sensitivity is out of range and needs cleaning.
See “Cleaning the SMCSM01-Z” on page 3.
Maintenance
alert
SMCSM01-Z failed power-up self test. Perform a sensitivity
test (see “Sensitivity Testing” on page 3). If the problem
persists, replace the SMCSM01-Z.
Low battery Batteries are low and must be replaced as soon as possible.
Congratulations! You have successfully installed
the SMCSM01-Z Smoke Sensor.