Operation Manual
23
3. Mount the Detector to the fixed part of the frame along the opening edge opposite the hinges using
either the double sided adhesive tape or screws provided.
If fixing the Detector with screws; fit the Keyhole slot in the top of the Detector over the head of the
smaller pan-head screw. Secure the bottom of the Detector using the 12mm countersunk head screw
fitted within the battery compartment. You will need to drill out the centre of the fixing screw hole using
a 3mm drill. Do not over tighten the fixing screws as this may distort or damage the casing.
4. Fit the Magnet to the moving part of the door/window opposite the Detector using the adhesive tape
or 15mm fixing screws.
Ensure that the parallel gap between the Magnet and Detector is less than 10mm and that the arrow
on the Magnet is pointing towards and aligned with the mark on the Detector.
5. If several windows need to be protected, remove the self-contained wired supplied and adopt the wire
according to the specifications as mentioned below. This should be wired to the terminal block
provided in the battery compartment in series connection. The wired contact should be connected
using two core (24AWG) wire of maximum length 1.5m.
A cable entry cut-out is available and adjacent to the terminal block.
6. Refit the battery cover.
SETTING THE MAGNETIC CONTACT DETECTORS
1. Located on the PCB of the Detector is a two-position DIP
switch (SW2).
2. DIP switches 1-2 are used to enable/disable the internal or
external wired magnetic contact. If setting the DIP1 & DIP2 to
‘Off’, only the internal contact will be active. When two
contacts are in use for internal and external connection
simultaneously, one activation will be counted if one of the
contacts is opened; while both contacts must be
all close, the Detector will then be treated as
close.
3. If external contacts are wired to the Detector, set
the DIP1 to ‘Off’ and DIP2 to ‘On’.
IMPORTANT: If external contacts are not
connected, set the DIP1 to ‘On’ and DIP2 to ‘Off’
for the detector to operate correctly.
4. In order to communicate with the Control Panel,
the ID code of the Detector needs to be learned by
the Control Panel. By pressing the tamper switch
either located adjacent to the PCB or rear cover of
the Detector will emit the ID code to the
Control Panel instantly, subject to the Control Panel being set at the Zone setup mode.










