Installation Instructions
4
• WSP wall sheathing must be a minimum 7/16 Category with an 
  APA Trademark that contains the consensus Standard DOC PS 2.
• 
Panel siding must be fastened with:
   - Minimum (0.092 inch shank diameter) hot-dip galvanized 
 ring shank nail, fastened in a grid a minimum of 8 inches 
   (203 mm) o.c. up to a maximum 16 inches (305 mm) o.c.                         
 grid depending on the wind pressure, wind speed and 
 wind exposure category limitations in 
APA Product 
   Report PR-N124
, Table 5a or 5b.
   - Fastener length must be long enough to fully penetration  
    WSP wall sheathing by at least 1/4 inch (6 mm). Ensure that
     the ring shanks of the nail fully engage the WSP sheathing. 
• Siding may be installed over exterior gypsum or foam sheathing. 
  The following precaution must be followed: 
   - Fastener length must be increased to ensure a minimum 
   1-1/2 inch (38 mm) penetration into structural framing or 
wood structural panel sheathing and structural framing; or
   -     For  alternate  fastening  option  to  wood  structural  panel   
   sheathing only, the nail length must be long enough to             
 fully penetrate 
sheathing by at least 
1/4 inch (6 mm).
 ○ Ensure that the ring shanks of the nail fully engage 
the wood structural panel sheathing.
   - A water-resistant barrier (WRB) is required in accordance  
     with building code requirements.
 ○ A drainage plane (example: furring strips, drainage 
mat or drainage board) may be required between 
       siding and WRB, consult local code requirements.
• Siding may be installed over low-compression foam sheathing. 
• Panel siding may be nailed directly over foam sheathing 
up to 1 
inch 
(25 mm) thick without a reduction in the allowable racking 
shear capacity (wall bracing capacity). 
P S I  F S
(R F I)     ( ) 
P  S  I    E  G  
  F S
 (R F I)
• When panel siding is NOT used as wall bracing, refer to IRC   
  Chapter 7 on Wall Covering for prescriptive siding attachment
over foam sheathing up to 4 inch (102 mm) thick direct to   
  wood framing or cold-formed steel framing. 
   - Section 703.15.1 for minimum fastening requirements         
         over foam sheathing to wood framing. 
 - Section 703.15.2 for furring minimum fastening   
 requirements over foam sheathing to wood framing.          
   - Section 703.16.1 for minimum fastening requirements        
   over foam sheathing to steel framing. 
 - 
Section 703.16.2 for furring minimum fastening   
requirements over foam sheathing into steel framing.
• LP assumes no liability for any loss or damage caused by the           
 IRC prescriptive design of the mechanical connection of the   
 siding to the structure and is expressly released by the  
   purchaser or owner from any such loss or liability.
  ( ) R--W  C I
1" (25 mm) min. 
clearance from 
roofi ng
Trim
Seal  bottom 
drip edges
4" (102 mm) min. 
vertical leg of 
step fl ashing 
Figure 4B
LAP
Siding
Framing (band joist, 
truss chord, etc.)
Wall Framing
1" (25 mm) 
min. overlap
Figure 4E
P S J D
BUTT & FLASH
Sloped 
fl ashing with 
4"  (102  mm) 
vertical leg
Siding
3/8" 
(10 mm) 
min. gap
Blocking
HORIZONTAL WALL JOINTS
Figure 4C
A F O  SIP A
 W S P W S
 (WSP)
P  S  I    F  S   
(R F I)     ( )  
•    In braced wall assemblies; 
 - Use a minimum (0.113 inch shank diameter) hot-dip   
  galvanized (ASTM A153) or equivalent nail for 38 Series 
                    and  76  Series  panel  siding.                                  
  - Use a minimum (0.131 inch shank diameter) hot-dip   
 galvanized (ASTM A153) or equivalent nail for 190 Series 
 panel siding.   
 - When using panel siding as both wall bracing and siding  
  consult Table 1 of 
APA Product Report PR-N124  o r        
ICC-ES Evaluation Report ESR-1301 for fastener spacing; 
  or consult a design professional. 
•  In non-braced wall assemblies; 
   - A minimum 0.092 inch smooth shank diameter nail may        
   be substituted depending on the wind pressure, wind 
 speed and wind exposure category limitations in 
PR-N124 or ESR-1301.
N I - D  S 
(CONT.)