GND
Ground
AU_2
Analog Input 0-10V #2
GND
Ground
AI_2
Analog Input 0-20mA #2
RS485/232
B/TX
B signal of RS485 bus or TX signal of COM Port (RS232)
GND
Ground
A/RX
A signal of RS485 bus or RX signal of COM Port (RS232)
1-WIRE
DATA
1-WIRE Data line
GND
Ground
VDD
1- WIRE Power line
EXT_PWR
GND
Ground
V_OUT
Switchable power supply for external sensors with overload and short circuit protection. Maximum
current load up to 500mA. The output voltage matches the V_IN input voltage.
EXT_OUT
DO_2
Discrete output 2, Open Drain to Ground up to 2A
GND
Ground
DO_1
Discrete output 1, Open Drain to Ground up to 2A
GND
Ground
EXT_PWR
V_IN
Input for connecting an external power supply. Voltage range from 5 to 55V
GND
Ground
3.4 User Interface
Smartico Industrial Sensor LoRaWAN has several user interface components:
LED Indicators for signaling
User Buttons for waking up the device and launching Application functions
Magnetic Sensor: to be used as a switch for external user actions, without a need to open the housing.
Internal Communication Interface: it contains the serial interface (UART) and is used to device
configuration or update firmware.
Figure 3: Internal Communication Interface
If there is no data cable supplied by the manufacturer, the customer can make the cable himself. To communicate with
the sensor, it is enough to use any UART to USB converter and connect to three contacts (UART_RX, UART_TX and GND).
The pinout of the connector is shown in the Table 5.