User Manual
SGCAN300 CANBUS RELAY MODULE USER MANUAL
SGCAN300 CANBUS Relay Module 2020-08-28 Version 1.0 Page 6 of 12
3 SPECIFICATION
Table 3 – Performance Parameter
Items
Contents
Operating Voltage
DC 8V~35V, Continuous Power Supply, DC Reverse Connection
Protection
Power Consumption
<2W
RS485 Port
Isolation, Half Duplex, Baud Rate: 9600bps and 19200bps are optional
CAN Port
Isolation, Baud Rate: 50kbps, 125kbps, 250kbps and 500kbps are optional
Optical Fiber Port
Max. Transmission Distance: 10km, Type: SC
Vibration
5 - 8 Hz: ±7.5 mm
8 - 500 Hz: 2 g
IEC 60068-2-6
Schock
50 g, 11 ms, half sine, finish the shock test from three directions.
There are total 18 shocks per test.
IEC 60068-2-27
Collision
25g, 16ms, half sine
IEC 60255-21-2
Case Dimensions
71.6mm x 92mm x 60.7mm
Installation
35mm Guide Rail Mounting
Working Conditions
Temperature: (-25~+70)°C Humidity: (20~93)%RH
Storage Condition
Temperature: (-30~+80)°C
Weight
0.2kg