DOUT16B-2 DIGITAL OUTPUT MODULE USER MANUAL
Chinese trademark English trademark SmartGen — make your generator smart SmartGen Technology Co., Ltd. No.28 Jinsuo Road Zhengzhou P. R. China Tel: +86-371-67988888/67981888/67992951 +86-371-67981000(overseas) Fax: +86-371-67992952 Web: www.smartgen.com.cn/ www.smartgen.cn/ Email: sales@smartgen.cn All rights reserved.
CONTENTS 1 2 3 4 5 OVERVIEW .......................................................................................................................................................4 TECHNICAL PARAMETERS ............................................................................................................................4 MODULE ADDRESS .........................................................................................................................................5 TERMINAL DIAGRAM ............
1 OVERVIEW DOUT16B-2 Digital Output Module is an expansion module which has 16 auxiliary digital output channels. Expansion module status is transmitted to DOUT16B-2 by main control board via RS485. 2 TECHNICAL PARAMETERS Table 2 Technical Parameters Items Contents Working Voltage DC8.0V~ DC35.0V continuous power supply Power Consumption <6W Aux. relay output port 1-16 10A relay for output port 1~4, 7~14. 16A relay for output port 5~6, 15~16. Case Dimension 161.6mm x 89.7mm x 60.
3 MODULE ADDRESS This is a 4-bit in-line DIP switch with 16 coding status, namely 16 module addresses (from 100 to 115). When it is turned to ON, the status is 1. The module address formula is Module Address=1A+2B+4C+8D+100. For example, when ABCD is 0000, the module address is 100. When ABCD is 1000, the module address is 101. When ABCD is 0100, the module address is 102. Similarly, when ABCD is 1111, the module address is 115. The corresponding module addresses of DIP switch are as follows.
4 TERMINAL DIAGRAM Fig.1 DOUT16B-2 Panel Diagram Table 1 Description of Rear Panel Terminal Connection No. Name Description Cable Size Remarks 1. B- DC power supply negative input 1.5mm2 DC power supply negative input. 2. B+ DC power supply positive input 1.5mm2 DC power supply positive input. 3. 120Ω 4. RS485B (-) 0.5 mm2 5. RS485A (+) RS485 communication port Twisted shielded line is used. If the terminal needs to match 120Ω resistance, terminal 3 and 4 need to be short circuited.
No. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. Name Remarks Volt free relay N/O output 1.5mm2 Capacity 250VAC/10A. Aux. output port 9 Volt free relay N/O output 1.5mm2 Capacity 250VAC/10A. Aux. output port 10 Volt free relay N/O output 1.5mm2 Capacity 250VAC/10A. Aux. output port 11 Volt free relay N/O output 1.5mm2 Capacity 250VAC/10A. Aux. output port 12 Volt free relay N/O output 1.5mm2 Capacity 250VAC/10A. Aux. output port 13 Volt free relay N/O output 1.
5 COMMUNICATION CONFIGURATION AND MODBUS COMMUNICATION PROTOCOL 5.1. RS485 COMMUNICATION PORT DOUT16B-2 is an expansion output module with RS485 communication port, which follows Modbus-RTU communication protocol. Communication Parameters Module Address 100 (range 100-115) Baud Rate 9600bps Data Bit 8-bit Parity Bit None Stop Bit 2-bit 5.2. INFORMATION FRAME FORMAT EXAMPLE 5.2.1. FUNCTION CODE 01H Slave address is 64H (decimal 100), read 10H (decimal 16) status of starting address 64H (decimal 100).
5.2.2. FUNCTION CODE 03H Slave address is 64H (decimal 100), starting address is 1 data of 64H (decimal 100) (2 bytes per data). Table 4 Example Data Address Address Data (Hex) 64H 1 Table 5 Function Code 03H Master Request Example Request Bytes Example (Hex) Slave address 1 64 Send to the slave 64H Function code 1 03 Read point register Starting address 2 00 Starting address is 64H 64 Count Number 2 00 Read 1 data (total 2 bytes) 01 CRC code CC CRC code which calculated by master.
5.2.3. FUNCTION CODE 05H Slave address is 64H (decimal 100), starting address is one status of 64H (decimal 100). Set 64H unit as 1. Table 7 Example Status Data Address Address Data(Hex) 64H 1 Illustration: Hex value FF00 forced status is 1. 0000H is forced as 0. Other values are illegal and do not affect the status.
5.2.4. FUNCTION CODE 06H Slave address is 64H (decimal 100), set one point content of starting address 64H (decimal 100) as 0001H. Table 10 Function Code 06H Master Request Example Request Bytes Example (Hex) Slave address 1 64 Send to the slave 64H Function code 1 06 Write single register Starting address 2 00 64 Starting address is 0064H Data 2 00 01 Set 1 point data (total 2 bytes) CRC code 2 00 20 CRC code which calculated by master.
5.3.
6 INSTALLATION Unit: mm Fig.