DIN16A Digital Input Module Version 1.1 2020-05-15 Page 8 of 10
No.
Function
Cable Size
Description
2.
DC input B+
2.5mm
2
DC power supply positive input.
3.
SCR
(CANBUS)
0.5mm
2
Connect CANBUS communication port to
expansion CAN port of HMC9000S.
Impedance-120Ω shielding wire with its one end
grounded is recommended. There is 120Ω terminal
resistance inside already; if needed, make terminal
5, 6 short circuits.
4.
CAN(H)
(CANBUS)
0.5mm
2
5.
CAN(L)
(CANBUS)
0.5mm
2
6.
120Ω
0.5mm
2
7.
DIN1
1.0mm
2
Digital input
8.
DIN2
1.0mm
2
Digital input
9.
DIN3
1.0mm
2
Digital input
10.
DIN4
1.0mm
2
Digital input
11.
DIN5
1.0mm
2
Digital input
12.
DIN6
1.0mm
2
Digital input
13.
DIN7
1.0mm
2
Digital input
14.
DIN8
1.0mm
2
Digital input
15.
COM(B-)
1.0mm
2
Connect to B- is allowed.
16.
DIN9
1.0mm
2
Digital input
17.
DIN10
1.0mm
2
Digital input
18.
DIN 11
1.0mm
2
Digital input
19.
DIN 12
1.0mm
2
Digital input
20.
DIN 13
1.0mm
2
Digital input
21.
DIN 14
1.0mm
2
Digital input
22.
DIN 15
1.0mm
2
Digital input
23.
DIN 16
1.0mm
2
Digital input
24.
COM(B-)
1.0mm
2
Connect to B- is allowed.
DIP
switch
SWITCH
Address selectionIt is module 1 when the switch 1
is connected to terminal 12 while module 2 when
connect to ON terminal.
Baud rate selection: It is 250kbps when the switch
2 is connected to terminal 12 while 125kbps when
connect to ON terminal.
LED
Indicator
INPUT STATUS
When DIN1~DIN16 input are active, corresponding
DIN1 ~ DIN16 indicators are illuminate.