DIN16A Digital Input Module Version 1.1 2020-05-15 Page 5 of 10
3 PROTECTION
3.1 WARNING
Warnings are not shutdown alarms and do not affect the operation of the gen-set. When DIN16A module is
enabled and detects the warning signal, the controller HMC9000S will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
Warning types are as follows:
Table 3 Warning Alarm List
No.
DET Range
Description
1
User-defined.
When the HMC9000S controller detects that the DIN16A
auxiliary input 1-16 alarm signal and the action set as
Warning”, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
(Each string of DIN16A input can be defined by users,
such as input port 1 defined as High Temp Warning,
when it is active, corresponding alarm information will
displayed on LCD.)
3.2 SHUTDOWN ALARM
When DIN16A module is enabled and detects the shutdown signal, the controller HMC9000S will initiate a
shutdown alarm and the corresponding alarm information will be displayed on LCD.
Shutdown alarms are as follows:
Table 4 Stop Alarm List
No.
Items
Detection Range
Description
1
DIN16A
Auxiliary
Input 1-16
User-defined.
When the HMC9000S controller detects that the DIN16A
auxiliary input 1-16 alarm signal and the action set as
“Shutdown”, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.
(Each string of DIN16A input can be defined by users,
such as input port 1 defined as High Temp Shutdown,
when it is active, corresponding alarm information will
displayed on LCD.)
Note: The types of shutdown alarm of auxiliary input port are effective only when users
configure them. Only emergency shutdown and overspeed shutdown work when the controller is
in override mode.
4 PANEL CONFIGURATION
Users can set the parameters of DIN16A via HMC9000S module. Pressing and holding button for